Fig. 6 - - Unit Leveling Tolerances
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition)
shall not exceed 87 Pa (0.35 in. wg) with economizer or
112 Pa (0.45 in. wg) without economizer.
"B"
F A
N
S I
D E
MAX WEIGHT
UNIT
KG
50TC-A07
336
50TC-D08
641
50TC-D09
693
50TC-D12
711
NOTES:
1. Dimensions in ( ) are in inches.
2. Hook rigging shackles through holes in base rail, as shown in detail "A." Holes in base rails are centered around the
unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
B-C
A-C
0.5" (13)
1.0" (25)
1.0" (25)
C06110
914-1371
(36"-54")
SEE DETAIL "A"
"C"
"A"
LB
MM
740
1890
1410
2235
1525
2235
1565
2235
Fig. 7 - - Rigging Details
For vertical ducted applications, secure all ducts to roof curb
and building structure. Do not connect ductwork to unit.
Insulate and weatherproof all external ductwork, joints,
and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through unconditioned spaces must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with
applicable fire codes.
For units with accessory electric
applications require a minimum clearance to combustible
surfaces of 25 mm (1- - in) from duct for first 305 mm (12- - in)
away from unit. Vertical applications do not require a
minimum clearance.
Minimum clearance is not required around ductwork.
PLACE ALL SEAL STRIP
IN PLACE BEFORE PLACING
UNIT ON ROOF CURB
DUCT END
DIMENSIONS
A
B
IN
MM
74.5
965
88.0
1040
88.0
1030
88.0
1015
10
heaters: Horizontal
DETAIL A
C
IN
MM
IN
38.0
850
33.5
41.0
1055
41.5
40.5
1255
49.5
40.0
1255
49.5
C09458