Carrier WeatherMaker 50TC07 Series Installation Instructions Manual

Carrier WeatherMaker 50TC07 Series Installation Instructions Manual

Single package rooftop cooling only with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaker 50TC07 Series:
Table of Contents

Advertisement

50TC*D/E units for installation in the United States contain use of Carrier's Staged Air Volume (SAV™) 2-speed
indoor fan control system. This complies with the U.S. Department of Energy (DOE) efficiency standard of 2018.
50TC*D/E units for installation outside the United States may or may not contain Carrier's Staged Air Volume
(SAV) 2-speed indoor fan control system as they are not required to comply with the U.S. Department of
Energy (DOE) 2018 mandatory efficiency standard.
50TC*M units for installation inside or outside the United States do not contain use of Carrier's Staged Air
Volume (SAV) 2-speed indoor fan motor control system as they comply with the U.S. Department of Energy
(DOE) 2018 mandatory efficiency standard without their use.
For specific details on operation of the Carrier SAV 2-speed indoor fan system, refer to the Variable Frequency
Drive (VFD) Factory-Installed Option 2-Speed Motor Control Installation, Setup, and Troubleshooting manual.
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rated Indoor Airflow (cfm) . . . . . . . . . . . . . . . . . . . . . 2
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Step 1 - Plan for Unit Location . . . . . . . . . . . . . . . . 15
Step 3 - Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . 16
Step 4 - Provide Unit Support . . . . . . . . . . . . . . . . . 16
Step 5 - Field Fabricate Ductwork . . . . . . . . . . . . . 20
Step 6 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . 20
Ductwork (when required). . . . . . . . . . . . . . . . . . . 21
Step 8 - Install Outside Air Hood . . . . . . . . . . . . . . 22
Electric Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500214-01
Installation Instructions
Printed in U.S.A.
Form 50TC-7-16-01SI
Single Package Rooftop Cooling Only
with Puron
®
• CO2 SENSOR WIRING
Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
Step 12 - Install Accessories . . . . . . . . . . . . . . . . . .81
Step 13 - Check Belt Tension . . . . . . . . . . . . . . . . .81
Pre-Start and Start-Up . . . . . . . . . . . . . . . . . . . . . . . .82
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . .CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, re-
pair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions
of cleaning coils and filters and replacing filters. All other op-
erations should be performed by trained service personnel.
Pg 1
8-19
WeatherMaker
50TC07-16
(R-410A) Refrigerant
Replaces: 50TC-7-01SI, 50TC-8-16-02SI
®

Advertisement

Table of Contents
loading

Summary of Contents for Carrier WeatherMaker 50TC07 Series

  • Page 1: Table Of Contents

    Energy (DOE) 2018 mandatory efficiency standard. 50TC*M units for installation inside or outside the United States do not contain use of Carrier’s Staged Air Volume (SAV) 2-speed indoor fan motor control system as they comply with the U.S. Department of Energy (DOE) 2018 mandatory efficiency standard without their use.
  • Page 2: General

    When working on air-conditioning equipment, observe precau- tions in the literature, tags and labels attached to the unit, and WARNING other safety precautions that may apply. Follow all safety codes, including ANSI (American National PERSONAL INJURY AND ENVIRONMENTAL Standards Institute) Z223.1. Wear safety glasses and work HAZARD gloves.
  • Page 3 Position: 9 10 11 12 13 14 15 16 17 18 Example: Unit Heat Type Packaging & Seismic Compliance 50 - Electric Heat Packaged Rooftop 0 = Standard 1 = LTL Model Series - WeatherMaker ® TC - Standard Efficiency Electrical Options A = None C = Non-Fused Disconnect...
  • Page 4 Fig. 2 — Dimensional Drawing for Units Built on and After 4/15/19 (Size 07)
  • Page 5 Fig. 3 — Dimensional Drawing for Units Built Prior to 4/15/19 (Size 07)
  • Page 6 Fig. 4 — Corner Weights and Clearances (Size 07)
  • Page 7 Fig. 5 — Base Rail Details (Size 07)
  • Page 8 Fig. 6 — Thru-the-Base Charts (Size 07)
  • Page 9 Fig. 7 — Unit Dimensional Drawing (Size 08, 09, 12)
  • Page 10 Fig. 7 —Unit Dimensional Drawing (Size 08, 09, 12) (cont)
  • Page 11 Fig. 8 — Unit Dimensional Drawing (Size 14)
  • Page 12 Fig. 8 —Unit Dimensional Drawing (Size 14) (cont)
  • Page 13 Fig. 9 — Unit Dimensional Drawing — Size 16 Unit...
  • Page 14 Fig. 9 — Unit Dimensional Drawing — Size 16 Unit (cont)
  • Page 15: Installation

    LOCATION DIMENSION CONDITION 48-in. (1219 mm) Unit disconnect is mounted on panel 18-in. (457 mm) No disconnect, convenience outlet option 18-in. (457 mm) Recommended service clearance 12-in. (305 mm) Minimum clearance 42-in. (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall) 36-in.
  • Page 16: Pad-Mounted Installation

    PAD-MOUNTED INSTALLATION Prepare pad and unit supports Check and tighten the bottom condensate drain connection plug Rig and place unit Convert unit to side-duct connection arrangement Install field-fabricated ductwork at unit duct openings Install outdoor air hood Install condensate line trap and piping Make electrical connections Install other accessories FRAME-MOUNTED INSTALLATION...
  • Page 17 Fig. 12 — Roof Curb Details - Size 07 Units...
  • Page 18 Fig. 13 — Roof Curb Details - Size 08-14 Units...
  • Page 19 Fig. 14 — Roof Curb Details - Size 16 Unit...
  • Page 20: Step 5 - Field Fabricate Ductwork

    FOR UNITS WITH ACCESSORY ELECTRIC HEATERS Step 5 — Field Fabricate Ductwork Cabinet return-air static pressure (a negative condition) shall All installations require a minimum clearance to combustible not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg surfaces of 1-in.
  • Page 21: Positioning On Curb (50Tc 07-14)

    Before setting the unit onto the curb, recheck gasketing on If the alternative condensate drain location through the bottom curb. of the unit is used in conjunction with a retrofit curb, the hole in the curb must be moved 12.5-in. (320 mm) towards the duct Rigging materials under unit (cardboard or wood to prevent end of the unit.
  • Page 22: 50Tc 16 Units

    50TC 16 UNITS REMOVABLE HORIZONTAL RETURN DUCT OPENING COVER Unit is shipped in the vertical duct configuration. Unit without factory-installed economizer or return-air smoke detector op- tion may be field-converted to horizontal ducted configuration using accessory CRDUCTCV002A00. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers.
  • Page 23 HOOD PARTS PANEL PLASTIC TIE WRAP QTY (2) PANEL CAULK HERE INDOOR INDOOR SCREWS FORMETAL TRAY COIL COIL QTY (2) ACCESS ACCESS PANEL PANEL Fig. 22 — Economizer and Two-Position Damper Fig. 23 — Indoor Coil Access Panel Relocation Hood Parts Location (Sizes 07-14) (Sizes 07-14) Economizer Hood and Two-Position Damper Hood Installa- tion (Size 07-14)
  • Page 24: 50Tc 16 Outside Air Hood

    50TC 16 OUTSIDE AIR HOOD Locate the (2) screws holding the metal tray to the basepan and remove. In order to remove the screws, it may be nec- Economizer Hood Removal and Setup – Factory Option essary to remove the panel underneath the two-position (Size 16) damper.
  • Page 25: Step 9 - Install External Condensate Trap And Line

    Replace the filter access panel. Step 9 — Install External Condensate Trap and Line The unit has one -in. condensate drain connection on the end of the condensate pan and an alternate connection on the bot- SIDE tom. See Fig. 32. Unit airflow configuration does not deter- PANEL mine which drain connection to use.
  • Page 26 Fig. 34 — 50TC 07 Control Wiring Diagram...
  • Page 27 Fig. 35 — 50TC 07 Power Wiring Diagram...
  • Page 28 Fig. 36 — 50TC-M08-12 Control Wiring Diagram...
  • Page 29 Fig. 37 — 50TC-D/E Wiring Diagram (08-14 Size Units)
  • Page 30 Fig. 38 — Single-Stage Cooling (without VFD) Power Wiring Diagram (Sizes 08-12)
  • Page 31 Fig. 39 — 2-Stage Cooling (with VFD) Power Wiring Diagram (Sizes 08-12)
  • Page 32 Fig. 40 — 2-Stage Cooling (with VFD) Power Wiring Diagram (Size 14)
  • Page 33 Fig. 41 — 50TC 16 Wiring Diagram...
  • Page 34 Fig. 42 — 2-Stage Cooling (with VFD) Power Wiring Diagram (Size 16)
  • Page 35 Fig. 43 — 50TC 07 Units Wiring Diagram with Humidi-MiZer ® System Option...
  • Page 36 ® Fig. 44 — 50TC 08-14 Units Wiring Diagram with Humidi-MiZer System Option...
  • Page 37 Fig. 45 — 50TC 16 Wiring Diagram with Humidi-MiZer ® System Option...
  • Page 38: Step 10 - Make Electrical Connections

    Step 10 — Make Electrical Connections 50TC 07-14 UNIT ELECTRICAL CONNECTIONS NOTE: See page 42 for 50TC 16 unit electrical connections. ELECTRIC DISCONNECT WARNING SWITCH COPPER ELECTRIC SHOCK HAZARD WIRE ONLY Failure to follow this warning could result in personal inju- ry or death.
  • Page 39: Field Wiring For 50Tc 07-14 Units

    Fig. 48 — NFD Handle and Shaft Assembly abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty. (Sizes 07-14) % Voltage Imbalance: When installing units, provide a disconnect switch per NEC max voltage deviation from average voltage (National Electrical Code) of adequate size.
  • Page 40 Non-powered type PWRD-CO This type requires the field installation of a general-purpose TRANSFORMER 125-v 15-A circuit powered from a source elsewhere in the CONVENIENCE building. Observe national and local codes when selecting wire OUTLET GFCI size, fuse or breaker requirements, and disconnect switch size and location.
  • Page 41 This device can be a thermostat (field-supplied) or a Premier- Link™ controller (available as factory-installed option or as Factory Option Thru-Base Connections field-installed accessory, for use on a Carrier Comfort Net- This service connection kit consists of a -in. electrical bulk-...
  • Page 42: 50Tc 16 Unit Electrical Connections

    50TC 16 UNIT ELECTRICAL CONNECTIONS Central Terminal Typical WARNING Board Thermostat Connections ELECTRIC SHOCK HAZARD Failure to follow this warning could result in personal inju- ry or death. Unit cabinet must have an uninterrupted, unbroken electri- cal ground to minimize the possibility of personal injury if an electrical fault should occur.
  • Page 43 Fig. 59 — Conduit into Control Box (Size 16) Fig. 62 — Mounting Position for Field Disconnects (up to 100A) (Size 16) Field power wires are connected to the unit at line-side pres- sure lugs at the main terminal block (TB1) or at factory- installed option non-fused disconnect switch.
  • Page 44: Field Wiring For 50Tc 16 Units

    Operation on improper line voltage or excessive phase im- balance constitutes abuse and may cause damage to electri- ELECTRIC cal components. Such operation would invalidate any ap- DISCONNECT plicable Carrier warranty. SWITCH COPPER WIRE ONLY Units Without Factory-Installed Disconnect When installing units, provide a disconnect switch of adequate ALUMINUM size per NEC (National Electrical Code).
  • Page 45: Convenience Outlets For 50Tc16 Units

    behind a hinged waterproof access cover, located on the panel be- neath the control box. See Fig. 67 and 68. Pwd-CO Fuse Switch Pwd-CO Transformer Convenience Outlet GFCI Disconnect Access Panel Fig. 67 — Convenience Outlet Location (Size 16) Fig. 65 — Location of Non-Fused Disconnect Non-powered type Enclosure (Size 16) This type requires the field installation of a general-purpose...
  • Page 46 installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate. NOTICE/AVIS The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket. Convenience Outlet Utilization Maximum Intermittent Use 15 - Amps DISCONNECT ALL POWER TO UNIT AND CONVE- Maximum Continuous Use 8 - Amps...
  • Page 47 (available as factory-installed option or as wire as it passes into the control box. Pull the wires over to the field-installed accessory, for use on a Carrier Comfort Network ® terminal strip at the upper left corner of the Central Terminal or as a stand alone control) or the RTU Open Controller for Board (CTB).
  • Page 48: Electric Heaters

    DISCONNECT EMT OR RIGID CONDUIT SINGLE CENTER MANUAL RESET MOUNTING (FIELD-SUPPLIED) POINT BOX POST LIMIT SWITCH LOCATION HEATER COVERS SINGLE POINT MAIN BRACKET AND HEATER HEATER HEATER CONTROL CONDUIT MOUNTING MODULE MODULE MOUNTING DRIP BOOT SCREW (LOCATION 1) (LOCATION 2) BRACKET CONTROL WIRE TERMINAL BLOCK Fig.
  • Page 49: 50Tc 16 Unit Electric Heaters

    CONTROL CONTL BOARD BUSHING SINGLE POINT BOX MOUNTING SCREWS DRIP BOOT BRACKET MOUNTING SCREWS POWER WIRES FOAM BUSHING HEATER RELAYS Field Connections HEATER MOUNTING Elec Htr SCREWS Fig. 78 — Typical Single Point Installation (Sizes 07-14) For simplicity, not all control wiring internal to the electric Low-Voltage Control Connections LS: Primary Limit Switch...
  • Page 50 SINGLE HEATER MANUAL RESET POINT BOX COVERS LIMIT SWITCH DISCONNECT MOUNTING LOCATION SINGLE POINT HEATER HEATER HEATER MODULE MODULE MOUNTING MOUNTING (LOCATION 1) (LOCATION 2) BRACKET SCREW Fig. 81 — Typical Component Location (Size 16) Heater and Supplementary Fuses When the unit MOCP device value exceeds 60-A, unit-mount- ed supplementary fuses are required for each heater circuit.
  • Page 51: Humidi-Mizer® System Control Connections

    CTB terminal R and the PINK lead to the LTLO switch with field-supplied wire nuts. Refer to the installation instructions included with the Carrier Edge Pro Thermidistat device for more information. 50TC 16 UNIT HUMIDI-MIZER To connect the Carrier humidistat (HL38MG029): Route the humidistat 2-conductor cable (field-supplied) through the bushing the unit’s louvered end panel (see...
  • Page 52 ® Fig. 86 — Edge ® Pro Thermidistat Fig. 87 — Typical Humidi-MiZer® Adaptive Dehumidification System Humidistat Wiring (50TC 07 Unit Shown)
  • Page 53 Fig. 88 — Typical Humidi-MiZer ® Adaptive Dehumidification System Humidistat Wiring (50TC 08-14 Units Shown)
  • Page 54 Fig. 89 — Typical Humidi-MiZer ® Adaptive Dehumidification System Humidistat Wiring (50TC 16 Units Shown)
  • Page 55: Economi$Er® X (Factory-Installed Option)

    Edge Programable Thermostat Unit CTB THERMOSTAT O/W2/B SRTN Humidi-MiZer™ FIOP *Connection not required. ® Fig. 90 — Typical Rooftop Unit with Humidi-MiZer Adaptive Dehumidification System with Edge ® Pro Thermidistat Device SYSTEM COMPONENTS ® EconoMi$er X (Factory-Installed Option) The EconoMi$er X system includes an economizer module, PRODUCT DESCRIPTION 20k mixed air sensor, damper actuator, and either a 20k out- The EconoMi$er X system is an expandable economizer con-...
  • Page 56: Inputs

    Relay Digital Output Rating at 30 vac (maximum power from ECONOMIZER MODULE WIRING DETAILS Class 2 input only) — 1.5A run: Use Fig. 92 and Tables 3 and 4 to locate the wiring terminals 3.5A inrush at 0.45PF (200,000 cycles) or for the Economizer module.
  • Page 57: S-Bus Sensor Wiring

    Table 4 — Economizer Module - Right Hand Terminal Table 5 — HH57AC081 Sensor Wiring Terminations Blocks TERMINAL TYPE DESCRIPTION LABEL TYPE DESCRIPTION NUMBER LABEL Top Right Terminal Blocks S-BUS Communications AUX2 I 24 vac IN The first terminal is not used. S-BUS S-BUS (Enthalpy Control...
  • Page 58: Menu Structure

    To use the keypad when working with menus: Press the (Enter) button to return to the current menu parameter. • Press the ▲ (Up arrow) button to move to the previous 10. Press the (Menu Up/Exit) button to return to the previ- menu.
  • Page 59 Table 7 — Menu Structure PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT FIRST STAGE COOLING DEMAND (Y1–IN) ECONO AVAIL YES/NO YES = economizing available; the system can use outside air for free cooling when required FIRST STAGE COOLING RELAY OUTPUT ECONOMIZING YES/NO YES = outside air being used for 1 stage cooling...
  • Page 60 Table 7 — Menu Structure (cont) PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT EXHAUST STAGE 2 RELAY OUTPUT EXH2 OUT ON/OFF Output of AUX terminal; displays only if AUX = EXH2 ENERGY RECOVERY VENTILATOR ON/OFF Output of AUX terminal; displays only if AUX = ERV MECH COOL ON Displays stage of mechanical cooling that is active.
  • Page 61 Table 7 — Menu Structure (cont) PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT INSTALL 01/01/10 Display order = MM/DD/YY Setting order = DD, MM, then YY. °F or °C UNITS DEG Sets economizer controller in degrees Fahrenheit or Celsius EQUIPMENT CONV Conventional or...
  • Page 62 Table 7 — Menu Structure (cont) PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT OAS T CAL 0.0 F ±2.5°F OUTSIDE AIR TEMPERATURE CALIBRATION Allows for the operator to adjust for an out of calibration tempera- ture sensor. OA H CAL 0% RH ±10% RH...
  • Page 63 Table 7 — Menu Structure (cont) PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT DMP CAL RUNNING DAMPER CALIBRATION ROUTINE RUNNING If DCV Auto enable has been programmed, when the W7220 is completing a calibration on the dampers, this alarm will display. Wait until the calibration is completed and the alarm will go away.
  • Page 64 Table 9 — Dry Bulb Operation without DCV (CO Sensor) — 1 Speed Fan DEMAND OUTSIDE AIR CONTROLLED GOOD TO Y1-I Y2-I Y1-O Y2-O OCCUPIED UNOCCUPIED SPEED VENTILATION (DCV) ECONOMIZE HIGH 0v/Off 0v/Off MIN POS Closed HIGH 24v/On 0v/Off MIN POS Closed HIGH 24v/On...
  • Page 65 Table 12 — Enthalpy Operation with DCV (CO Sensor) — 1 Speed Fan DEMAND OUTSIDE AIR CONTROLLED GOOD TO Y1-I Y2-I Y1-O Y2-O OCCUPIED UNOCCUPIED SPEED VENTILATION (DCV) ECONOMIZE HIGH 0v/Off 0v/Off VENTMIN Closed HIGH 24v/On 0v/Off VENTMIN Closed HIGH 24v/On 24v/On VENTMIN...
  • Page 66 Table 15 — Enthalpy Operation without DCV (CO Sensor) — 2 Speed Fan DEMAND OUTSIDE AIR CONTROLLED GOOD TO Y1-I Y2-I Y1-O Y2-O OCCUPIED UNOCCUPIED SPEED VENTILATION (DCV) ECONOMIZE 0v/Off 0v/Off MIN POS Closed 24v/On 0v/Off MIN POS Closed HIGH 24v/On 24v/On MIN POS...
  • Page 67: Enthalpy Settings

    Table 17 — Single Enthalpy and Dual Enthalpy High Limit Curves POINT P1 POINT P2 ENTHALPY TEMP. DRY TEMP. ENTHALPY HUMIDITY HUMIDITY CURVE BULB (F) DEWPOINT (F) (btu/lb/da) TEMP. (F) TEMP. (F) (%RH) (%RH) 28.0 36.8 66.3 80.1 26.0 39.6 63.3 80.0 24.0...
  • Page 68: Troubleshooting

    The unit pauses and then displays IN PROGRESS. Press the (Enter) button. When the test is complete, DONE appears. ALARM ERASED displays. When all desired parameters have been tested, press the Press the (Menu up/Exit) button to complete the (Menu Up) button to end the test. action and return to the previous menu.
  • Page 69 Fig. 97 — Typical PremierLink™ Control Wiring Diagram, Size 07 Shown...
  • Page 70 Fig. 98 — 50TC*M08-12 PremierLink™ Control Wiring Diagram...
  • Page 71 Fig. 99 — Typical PremierLink™ Control Wiring Diagram, Dual Compressor Sizes 08-12 shown...
  • Page 72 ® Fig. 100 — Typical PremierLink™ Control Wiring Diagram with Humidi-MiZer System Option...
  • Page 73 Fig. 101 — Typical RTU Open Controller Wiring Diagram - 50TC 07 Units...
  • Page 74 Fig. 102 — 50TC-M08-12, RTU Open Controller Wiring Diagram...
  • Page 75 Fig. 103 — Typical RTU Open Controller Wiring Diagram — 50TC-D/E08-14 Units...
  • Page 76 Fig. 104 — RTU Open Controller Wiring Diagram — 50TC 16 Unit...
  • Page 77 ® Fig. 105 — Typical RTU Open Controller Wiring Diagram with Humidi-MiZer System Option - 50TC 07 Units...
  • Page 78 Fig. 106 — Typical RTU Open Controller Wiring Diagram with Humidi-MiZer ® System Option — 50TC 08-14 Units...
  • Page 79 Fig. 107 — Typical RTU Open Controller Wiring Diagram with ® Humidi-MiZer System Option — 50TC 16 Units...
  • Page 80: Smoke Detectors

    ADDITIONAL APPLICATION DATA Smoke Detectors Smoke detectors are available as factory-installed options on Refer to the Application Data sheet, Factory-Installed Smoke 50TC models. Smoke detectors may be specified for supply-air Detectors for Small and Medium Rooftop Units 2 to 25 Tons only, for return-air without or with economizer, or in combina- for discussions on additional control features of these smoke tion of supply-air and return-air.
  • Page 81: Step 11 - Adjust Factory-Installed Options

    Unit Without Economizer or Economizer 2 Position Damper 2 Position Damper Fig. 110 — EconoMi$er ® IV Wiring • Single point kits Step 11 — Adjust Factory-Installed Options • Low Ambient Controls SMOKE DETECTORS • Thermostat / Sensors Smoke detector(s) will be connected at the Controls Connec- •...
  • Page 82: Belt Tension Method

    BLOWER PULLEY V-BELT MOTOR PULLEY MOTOR BELT DEFLECTION FORCE (LBS) BELT SMALLEST UNNOTCHED CROSS SHEAVE NOTCHED BELTS BELTS MOUNTING SECTION DIAMETER USED USED MOTOR MOUNTING BOLTS (4) 3.0-3.6 PLATE A, AX 3.8-4.8 Fig. 112 — Belt Drive Motor Mounting 5.0-7.0 3.4-4.2 —...
  • Page 83 Fig. 113 — UltraTech Scroll Compressor...
  • Page 86 © Carrier Corporation 2019 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500214-01 Printed in U.S.A. Form 50TC-7-16-01SI Pg 86 8-19 Replaces: 50TC-7-01SI, 50TC-8-16-02SI...
  • Page 87 START-UP CHECKLIST FOR 50TC 07-16 ONLY (Remove and use for job file) NOTE: To avoid injury to personnel and damage to equipment or prop- erty when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sections of this Installation Instructions document.
  • Page 88 10. Restore set-points for thermostat and humidistat (Y/N) _____ REPEAT PROCESS FOR 2 COMPRESSOR SYSTEMS. © Carrier Corporation 2019 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500214-01 Printed in U.S.A.

Table of Contents