Rtu-Mp Controller Inputs And Outputs - Carrier 50TC Installation Instructions Manual

Single package rooftop, 50hz cooling only sizes 07, 08, 09, and 12 with puronr (r-410a) refrigerant
Hide thumbs Also See for 50TC:
Table of Contents

Advertisement

POINT NAME
Space Temperature Sensor
Supply Air Temperature
Local Outside Air Temperature Sensor
Space Temperature Offset Pot
Indoor Air Quality
Outdoor Air Quality
Safety Chain Feedback
Compressor Safety
Fire Shutdown
Enthalpy Switch
Humidistat Input Status
Space Relative Humidity
Outside Air Relative Humidity
Supply Fan Status
Filter Status
Remote Occupancy Input
Economizer Commanded Position
Supply Fan Relay State
Compressor 1 Relay State
Compressor 2 Relay State
Heat Stage 1 Relay State
Heat Stage 2 Relay State
Power Exhaust Relay State
Dehumidification Relay State
LEGEND
AI
--- Analog Input
AO --- Analog Output
DI
--- Discrete Input
DO --- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Parallel pins J5--- 1 = J2--- 6, J5--- 3 = J1--- 10, J5--- 5 = J1--- 2 are used for field --- installation.
The RTU- - MP controller requires the use of a Carrier
space sensor. A standard thermostat cannot be used with
the RTU- - MP system.
Supply
Air
Temperature
FIOP- - equipped 50TC unit, the unit is supplied with a
supply- - air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 152 mm
(6- - inches) in length. It is a nominal 10- - k ohm thermistor.
The SAT is factory- - wired. The SAT probe is wire- - tied to
the supply- - air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re- - position the sensor in the flange of the supply- - air
opening or in the supply air duct (as required by local
codes). Drill or punch a 12.7 m
or duct. Use two field- - supplied, self- - drilling screws to
secure the sensor probe in a horizontal orientation. See
Fig. 28.
Table 9 – RTU- - MP Controller Inputs and Outputs
BACnet OBJECT
NAME
INPUTS
sptsens
sat
oatsens
sptopot
iaq
oaq
safety
compstat
firedown
enthalpy
humstat
CONFIGURABLE INPUTS*
sprh
oarh
fanstat
filtstat
remocc
OUTPUTS
econocmd
sf
comp_1
comp_2
heat_1
heat_2
aux_2
humizer
(SAT)
Sensor
- -
On
(1
/
- - in.) hole in the flange
2
TYPE OF I/O
AI (10K Thermistor)
AI (10K Thermistor)
AI (10K Thermistor)
AI (100K Potentiometer)
AI (4---20 ma)
AI (4---20 ma)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
AI (4---20 ma)
AI (4---20 ma)
DI (24 VAC)
DI (24 VAC)
DI (24 VAC)
4---20ma
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC , 1A)
DO Relay (24VAC, 1A)
Outdoor Air Temperature (OAT) Sensor - - The OAT is
factory- - mounted
in
the
accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring.
EconoMi$er2 - - The RTU- - MP control is used with
EconoMi$er2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the RTU- - MP control; EconoMi$er2 has no internal
logic device.
Outdoor air management functions can be enhanced with
field- - installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
sensor
2
Outdoor air CO
sensor
2
29
CONNECTION PIN
NUMBERS
J20---1, 2
J2---1, 2
J2---3, 4
J20---3
J4---2, 3
J4---5, 6
J1---9
J1---2
J1---10
J2---6, 7
J5---7, 8
J4---2,3 or J4---5,6
J5---1,2 or J5---3,4 or
J5 5,6 or J5---7,8
J2---5
J1---4
J1---8
J1---7
J1---6
J1---5
J11---3
J11---7, 8
EconoMi$er2
(FIOP
or