Outdoor Air Temperature (OAT) Sensor — The OAT is
factory- - mounted
in
the
accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring.
EconoMi$er2 — The PremierLink control is used with
EconoMi$er2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the PremierLink control; EconoMi$er2 has no internal
logic device.
Outdoor air management functions can be enhanced with
field- - installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
sensor
2
Outdoor air CO
sensor
2
Refer to Table 4 for accessory part numbers.
Field connections — Field connections for accessory
sensor and input devices are made at the 16- - pole terminal
APPLICATION
Differential Dry Bulb
Temperature with
PremierLink
(PremierLink requires
4---20 mA Actuator)
Single Enthalpy with
PremierLink
(PremierLink requires
4---20mA Actuator)
Differential Enthalpy
with PremierLink
(PremierLink requires
4---20mA Actuator)
NOTES:
CO
Sensors (Optional):
2
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 --- Aspirator box used for duct--- mounted CO
33ZCT55CO2
--- Space temperature and CO
33ZCT56CO2
--- Space temperature and CO
EconoMi$er2
(FIOP
Table 4 – PremierLink Sensor Usage
OUTDOOR AIR
TEMPERATURE
TEMPERATURE
SENSOR
Included ---
CRTEMPSN001A00
Included ---
Not Used
Included ---
Not Used
2
room sensor with override.
2
room sensor with override and setpoint.
2
block (TB1) located on the control box bottom shelf in
or
front of the PremierLink control (See Fig. 29). Some input
devices also require a 24- - vac signal source; connect at
CTB terminal R at "THERMOSTAT" connection strip for
this signal source. See connections figures on following
pages for field connection locations (and for continued
connections at the PremierLink board inputs).
Table 5 provides a summary of field connections for units
equipped with Space Sensor. Table 6 provides a summary
of field connections for units equipped with Space
Thermostat.
Space
Sensors
factory- - shipped configured for Space Sensor Mode. A
Carrier T- - 55 or T- - 56 space sensor must be used. T- - 55
space temperature sensor provides a signal of space
temperature to the PremierLink control. T- - 56 provides
same space temperature signal plus it allows for
adjustment of space temperature setpoints from the face of
the sensor by the occupants.
RETURN AIR
OUTDOOR AIR
ENTHALPY SENSOR
SENSOR
Required ---
33ZCT55SPT
or equivalent
Requires ---
---
HH57AC077
or equivalent
Requires ---
---
HH57AC077
or equivalent
room sensor.
20
- -
The
PremierLink
controller
RETURN AIR
ENTHALPY SENSOR
---
---
---
Requires ---
HH57AC078
or equivalent
is