Integrating the Vitotronic control unit into LON
Vitotronic 300
Control unit is fault manager
Parameter/code "79:1" in the "Gen-
eral" group
Viessmann system number
Parameter/code "98:1" in the "Gen-
eral" group
LON subscriber fault monitoring
Parameter/code "9C:20" in the
"General" group
Updating LON subscriber list
Vitotronic control unit installation and service
instructions
Carrying out subscriber check
Vitotronic control unit installation and service
instructions
Commissioning the Vitogate
Devices required for commissioning:
■
PC/laptop with the following equipment:
–
Minimum screen resolution 1024 x 768
Integral or external Ethernet network module
–
PDF Reader
–
Supported web browsers: Mozilla Firefox version 60
■
to 62 on Microsoft Windows version 7 or 10
■
Crossed network cable
Making the connection to the Ethernet network
Connect the computer network card to the RJ45 LAN
connection of the Vitogate 300 by means of a crossed
network cable.
Enabling the DHCP server
Dynamic Host Configuration Protocol (DHCP) makes
IP addresses available to clients on request.
The DHCP server of the Vitogate 300 can be used to
provide an IP address if the computer has been set up
as DHCP client (standard setting).
Press and hold the reset button on the Vitogate 300 for
at least 10 s, but no longer than 15 s.
The DHCP server has been activated once the status
indicator flashes green/red alternately.
(cont.)
Vitotronic 200-H
Control unit is not fault manager.
Code "79:0"
Viessmann system number
Code "98:1"
LON subscriber fault monitoring
Code "9C:20"
Note
If a configuration file is to be loaded via a PC for sev-
eral gateways within a network, a pause of at least ten
minutes must be observed between the applications.
Alternatively, the ARP cache of the PC can be deleted
between the applications.
Note
The DHCP server does not need to be activated if a
static IP address is to be used.
Commissioning and adjustment
Vitogate 300
Device is fault manager.
—
—