Viessmann VITOGATE 200 Installation And Service Instructions Manual

Viessmann VITOGATE 200 Installation And Service Instructions Manual

Communication for heating systems via knx/eib systems

Advertisement

Quick Links

VIESMANN
Installation and service
instructions
for contractors
Vitogate 200
Type EIB
Communication for heating systems via KNX/EIB systems
For applicability, see the last page
VITOGATE 200
Please keep safe.
5592 880 GB
6/2007

Advertisement

Table of Contents
loading

Summary of Contents for Viessmann VITOGATE 200

  • Page 1 VIESMANN Installation and service instructions for contractors Vitogate 200 Type EIB Communication for heating systems via KNX/EIB systems For applicability, see the last page VITOGATE 200 Please keep safe. 5592 880 GB 6/2007...
  • Page 2: Safety Instructions

    Safety instructions Safety instructions Please follow these safety instructions closely to prevent accidents and mate- rial losses. Safety instructions explained ■ all current safety regulations as defined by DIN, EN, DVGW, TRGI, Danger TRF, VDE and all locally applicable This symbol warns against the standards, risk of injury.
  • Page 3 ■ When using gas as fuel, also close the For replacements, use only orig- main gas shut-off valve and safeguard inal spare parts from Viessmann against unauthorised reopening. or those which are approved by ■ Isolate the system from the power sup- Viessmann.
  • Page 4 Communication objects and flags................ 15 Parameters in ETS....................18 Troubleshooting BUS voltage/mains power failure................. 26 Characteristics after restoration of BUS voltage/mains power......26 Connection fault between the Vitogate 200 and the EIB or LON system..... 26 Designs Connection diagram..................... 27 Specification....................... 28 Certificates Declaration of conformity..................
  • Page 5 Preparing for installation Preparing for installation Product information The Vitogate 200 type EIB gateway is The Vitogate 200, type EIB must be inte- designed to hook up Vitotronic control grated into the KNX/EIB system by an units with integral LON communication authorised specialist.
  • Page 6 Connection to the Vitotronic control unit The Viessmann LON is designed for the "Line" BUS topology with a terminator at both ends (accessories). For free wiring with a central terminator (BUS terminator), please see the "Viessmann LON manual" at www.viessmann.de/lon.
  • Page 7 Connection with LON cable Routing distance ≤ 7 m A Vitotronic control unit C Terminator B Vitogate 200, type EIB D LON cable, 7 m long Connection with LON cable and LON coupling Routing distance 7 to 21 m A Vitotronic control unit...
  • Page 8 ≤ 900 m Routing distance ≤ 900 m (with LON plug) A Vitotronic control unit D LON plug B Vitogate 200, type EIB E On-site cable C Terminator F Up to 99 subscribers Connection with LON cable, on-site cable and LON socket ≤...
  • Page 9: Power Supply

    Power supply via the main isolator When the heating system is switched off No data is transferred to the EIB sys- via the main isolator, the Vitogate 200, tem. type EIB and the Vitotronic control unit are also switched off.
  • Page 10 Power supply independent of the main isolator When the heating system is switched off No data is transferred to the EIB sys- via the main isolator, the Vitogate 200, tem. type EIB remains on, whilst the Vitotronic control unit is switched off.
  • Page 11 Installation sequence Power supply (cont.) F Vitrotronic control unit power supply (plug fÖ) 1. Check whether the power cable to the 3. Insert plug fÖ into the Vitotronic con- Vitotronic control unit has appropriate trol unit. fuse protection. 2. Connect the power cable on site inside junction box D and at plug fÖ.
  • Page 12: Display And Control Elements

    (accessory) must be plugged into the The data transfer via the LON system Vitotronic control unit. can take several minutes. Viessmann system number and subscriber number Set LON system number, LON sub- Note scriber number and further functions via Each number can only be allocated once code 2.
  • Page 13 Vitotronic control unit LON integration (cont.) Example: Single boiler system with control unit Vitotronic 300, type GW2 (V300GW2); heating circuit control unit Vitotronic 200-H, type HK3 (V050HK3) installed downstream and Vitogate 200, type EIB Vitotronic 300 Vitotronic 200-H Vitogate 200 Subscriber no.
  • Page 14 The EIB product database for the Vito- Download the EIB product database and gate 200, type EIB can be downloaded then import it into the EIB Tool software from www.viessmann.de/vito- (ETS). Only then can the parameters for gate-200-eib. the communication objects be set for the...
  • Page 15 Commissioning EIB product database (cont.) The Vitogate 200, type EIB must be inte- grated into the KNX/EIB system by an authorised specialist; this is not part of the standard delivery from Viessmann. Characteristics after download A full reset is triggered after each down- The configuration is retained.
  • Page 16 Commissioning Communication objects and flags (cont.) 8: Betriebsart EIS6 - A1: Betriebsart EIS6 9: Betriebsart EIS6 - A1: Betriebsart EIS6 10: Betriebsart EIS6 - A1: Betriebsart EIS6 11: Betriebsart EIS6 - A1: Betriebsart EIS6 12: Betriebsart EIS6 - A1: Betriebsart EIS6 13: Betriebsart EIS6 - A1: Betriebsart EIS6 14: Betriebsart EIS6 - A1: Betriebsart EIS6 15: Betriebsart EIS6 - A1: Betriebsart EIS6...
  • Page 17 Commissioning Communication objects and flags (cont.) Flags for read only datapoints (delivered condition) Flags for write only datapoints (delivered condition) Explanation of flags Flag Explanation Kommunikation (Com- Authority for communication with EIB system (corresponds munication) to a main switch) Lesen (Read) Read request via EIB system, if the group address in this communication object stands in first position.
  • Page 18 Aktualisieren (Update) For automatic updates following a power failure Parameters in ETS With the Vitogate 200, type EIB, up to 32 The heating system fault messages are communication objects can be pro- transferred in the form of an error bit and/ cessed by the Vitotronic control units in or an error byte.
  • Page 19 Commissioning Parameters in ETS (cont.) Datapoints Example with ETS3 The following parameters can be set for 7. Zykluszeit (Cycle time) each communication object: 8. max Abweichung gegenüber zuletzt 1. Regelung (Control unit) gesendeten Wert (max deviation from 2. Anlagen Nummer (System number) the value transmitted last) 3.
  • Page 20 Vitotronic 200, type HO1 2. Anlagen Nummer Note The Viessmann system number must Menu for the selection of the Viessmann also be programmed into the Vitotronic system number to be assigned to the control unit selected under "Regelung" corresponding communication object.
  • Page 21 Menu for the selection of the function to unit selected under "Regelung" (for cod- be assigned to the corresponding com- ing, see page 13). munication object. Vitogate 200, type EIB is factory-set to subscriber number "98" (delivered con- dition). Menu selection Function...
  • Page 22 Heizkreis M3 (Heating circuit M3) Warmwasser (DHW) Solar Datapoints overview: The list can be Datapoints overview: The list can be downloaded from www.viessmann.de/ downloaded from www.viessmann.de/ vitogate-200-eib. vitogate-200-eib. 6. Datenpunkt 7. Zykluszeit Menu for the selection of a datapoint to...
  • Page 23 Commissioning Parameters in ETS (cont.) Menu selection Explanation nie senden (Never The value of this datapoint is never transmitted to the EIB transmit) system. bei jeder Änderung sen- The value of this datapoint is transmitted to the EIB system den (transmit after every following any change.
  • Page 24: Error Byte

    Commissioning Parameters in ETS (cont.) Menu selection Explanation 5 s bis 120 min (5 s to The fault message is transmitted cyclically to the EIB sys- 120 min) tem in accordance with the selected interval. nicht zyklisch senden The fault message is either never transmitted to the EIB (do not transmit cycli- system or only in the case of a change.
  • Page 25 (cont.) Any fault on a component of the heating A list of fault codes can be downloaded system can trigger the transmission of a from www.viessmann.de/vito- "Fehlerbyte" error byte to an appropriate gate-200-eib. central fault message facility. However, this requires the fault message to be...
  • Page 26: Lon System

    EIB system. The communication again. objects and their values (if available) are automatically updated. Connection fault between the Vitogate 200 and the EIB or LON system EIB system If the connection between the Vito- gate 200 and the EIB system is interrup- ted, fault code "98"...
  • Page 27: Connection Diagram

    Designs Connection diagram L1 N 230V~ 28V– A LON connection C 230 V~ power supply 2 pce RJ45 sockets, screened 2-pole terminal B EIB 28 V– connection Type: Phoenix MKDSP3/2-5.08 2 Wago solder pins (part no. 243-131) for fitting the Wago EIB terminal...
  • Page 28: Specification

    Specification Specification Mains voltage 230 V ~ BUS voltage 29 V – Power consumption Protection class IP rating IP 20 to EN 60529; ensure through appropriate design and installation Function Type 1 B as per EN 60730-1 Permiss. ambient tempera- ture ■...
  • Page 29: Declaration Of Conformity

    Certificates Declaration of conformity We, Viessmann Werke GmbH&Co KG, D-35107 Allendorf, confirm as sole respon- sible body that the product Vitogate 200, type EIB complies with the following stand- ards: DIN EN 50090-2-2 (1997-06) DIN EN 61000-6-2 (2002-08) DIN EN 55024 (2003-10)
  • Page 30 Keyword index Keyword index Error byte...........24 Applicability notice......32 ■ Download........15 BUS voltage failure......26 BUS voltage restoration.....26 Fault manager........13 Flags..........15 ■ Explanation........17 Central fault message......23 ■ Read..........17 Communication objects......15 ■ Write..........17 Connection to Vitotronic control unit ■ Via LON..........6 Control elements........12 Group..........21 Control panel........6 Control units.........5...
  • Page 31 Keyword index Keyword index (cont.) Parameters........18 Reset..........12 ■ Anlagen Nummer......20 ■ Datenpunkt........22 ■ Dienst..........21 Service..........21 ■ Gruppe..........21 Standard setting.........12 ■ Max Abweichung......22 Status display EIB system....12 ■ Regelung........19 Subscriber number......20 ■ Teilnehmer-Nummer.......20 System number........20 ■ Zykluszeit........22 Power supply ■ Guidelines.........9 Transmission interval.....22, 23, 25 ■...
  • Page 32 Applicability Vitogate 200, type EIB Part no. 7247 637 Only in conjunction with Viessmann boiler and heating circuit control units. Viessmann Werke GmbH&Co KG Viessmann Limited D-35107 Allendorf Hortonwood 30, Telford Telephone: +49 6452 70-0 Shropshire, TF1 7YP, GB Fax: +49 6452 70-2780 Telephone: +44 1952 675000 www.viessmann.com...