Maintenance
(cont.)
Changing the rotational direction of the mixer motor (if required)
gS
|
BU
~
Fig. 53
Check flow temperature sensor
20
10
8
6
4
2
1
0.8
0.6
0.4
10
30
50
Temperature in °C
Fig. 54
Sensor type: NTC 10 k

Checking the Vitotronic 200-H (accessories)

The Vitotronic 200-H is connected to the control unit
via the LON system. To test the connection, carry out a
subscriber check at the boiler control unit (see
page 41).
70
90
110
Ω
1. Remove the upper casing cover of the extension
kit.
Danger
An electric shock can be life-threatening.
Before opening the boiler, disconnect it from
the mains voltage, e.g. at the fuse or mains
isolator.
2. At plug
, swap the cores at terminals "
gS
"
".
~
3. Refit the casing cover.
1. Disconnect plug
(flow temperature sensor).
?
2. Check the sensor resistance and compare it to the
curve.
In the event of severe deviation replace the sensor.
Troubleshooting
" and
|
79