Installation sequence

Installing the oil supply as a single line system

A
Fig. 6
Fuel oil filter with automatic air vent valve
A
Foot valve
B
Important: Install a single line fuel oil filter R
grade max. 40
m) and a fuel oil air vent valve in the
µ
oil supply.
Recommendation:
Automatic fuel oil air vent valve with filter: FloCo-
Optimum-K (filter grade 5
For replacement during maintenance work: Micro-
tec MC-18 oil filter element (filter grade 5
See Vitoset pricelist.
For tanks sited below the oil burner pump:
If the suction head or the max. pipe length is greater
than specified in the following table, install an oil feed
pump with intermediate tank in the immediate proxim-
ity of the boiler.

Opening the control unit enclosure

!
Please note
Electronic assemblies can be damaged by elec-
trostatic discharge.
Prior to commencing any work, touch earthed
objects such as heating or water pipes to dis-
charge static loads.
12
B
(filter
m).
µ
m).
µ
Sizing the oil line
Suction
Max. pipe length in m for suction
head H in m
line internal diameter
4 mm
+4.0
100
+3.5
95
+3.0
89
+2.5
83
+2.0
77
+1.5
71
+1.0
64
+0.5
58
0.0
52
-0.5
46
-1.0
40
-1.5
33
-2.0
27
-2.5
21
-3.0
15
-3.5
-4.0
Note
For the oil line, select the smallest diameter required
for the suction head.
5 mm
6 mm
100
100
100
100
100
100
100
100
100
100
97
81
66
51
36
9
21
6
100
100
100
100
100
100
100
100
100
100
100
100
100
100
75
44
12