Layout Examples; Plastic (Pps) Balanced Flue System (Connection Line) For Connecting Multiple Flues To A Single Balanced Flue System - Viessmann Vitodens 100-W Technical Manual

Flue systems for gas condensing boilers vitodens series; vitosolar series up to 150.0 kw
Hide thumbs Also See for Vitodens 100-W:
Table of Contents

Advertisement

Design and sizing information for connection on the flue gas side
2
A Ventilation air
B Flue gas
C Inspection port

Layout examples

Minimum clearances of the individual flues to DIN V 18160-1:
■ In square/rectangular shafts: 20 mm
■ In round shafts: 30 mm
20
a
20
b
2.10 Plastic (PPs) balanced flue system (connection line) for connecting multiple flues
to a single balanced flue system
Vitodens condensing boilers meet the safety requirements of
DIN 3368-6.
Therefore, general approval by the building inspectorate for connec-
tion to a balanced flue system is not required [Germany].
VIESMANN
30
B
≥ 30
A
≈ 150
C
a
20
20
a
20
a
d
System size
Dimensions [mm]
Ø mm
a
60
73
80
94
110
128
Note
According to the approval certificate, internal shaft dimensions
smaller than those shown in the table may also be used, provided
this is allowed under performance verification to EN 13384.
When connecting 2 condensing boilers to one chimney on the same
floor, the connection piece inlets should be separated by at least
300 mm.
Design and calculations for balanced flue systems with multiple con-
nections are carried out by the relevant manufacturer.
(cont.)
20
a
20
b
c
d
206
113
299
248
134
362
316
168
464
VITODENS, VITOSOLAR