Standard Maintenance; Level 1 Maintenance; Level 2 Maintenance; Level 3 (Or Higher) Maintenance - Carrier AquaSnap 61AF 022 Installation, Operation And Maintenance Instructions

High-temperature heat pumps
Table of Contents

Advertisement

15 - STANDARD MAINTENANCE

The heat pumps must be maintained by professional technicians,
whilst routine checks can be carried out locally by specialised
technicians. See the standard EN 378-4.
All refrigerant charging, removal and draining operations
must be carried out by a qualified technician and with the
correct material for the unit. Any inappropriate handling can
lead to uncontrolled fluid or pressure leaks.
WARNING: Before doing any work on the machine ensure
that the power is switched off. If a refrigerant circuit is opened,
it must be evacuated, recharged and tested for leaks. Before
any operation on a refrigerant circuit, it is necessary to
remove the complete refrigerant charge from the unit with a
refrigerant charge recovery group.
Simple preventive maintenance will allow you to get the best
performance from your heat pump unit:
- improved heating performance
- reduced power consumption
- prevention of accidental component failure
- prevention of major time-consuming and costly interventions
- protection of the environment
There  are  five  maintenance  levels  for  the  heat  pump  units,  as 
defined by the AFNOR X60-010 standard.

15.1 - Level 1 maintenance

See note on the next page. Simple procedures, can be carried
out by the user on a weekly basis:
- Visual inspection for oil traces (sign of a refrigerant leak),
- - Air heat exchanger (evaporator) cleaning - see chapter
'Evaporator coil - level 1',
- Check for removed protection devices, and badly closed doors/
covers,
- Check the unit alarm report when the unit does not
- work (see 61AF SmartVu
- General visual inspection for any signs of deterioration,
- Verify the charge in the sight-glass,
- Check that the temperature difference between the heat
exchanger inlet and outlet is correct.

15.2 - Level 2 maintenance

This level requires specific know-how in the electrical, hydraulic 
and mechanical fields. It is possible that these skills are available 
locally: existence of a maintenance service, industrial site,
specialised subcontractor.
The frequency of this maintenance level can be monthly or annually
depending on the verification type.
In these conditions, the following maintenance operations are
recommended.
Carry out all level 1 operations, then:Electrical checks
- At least once a year tighten the power circuit electrical screw
connections (see table with tightening torques).
- Check and retighten all control/command screw connections,
if required (see table with tightening torques).
- Remove the dust and clean the interior of the control boxes,
if required.
- Check the status of the contactors and disconnect switches.
- Check the presence and the condition of the electrical
protection devices.
- Check the correct operation of all heaters.
- Replace the fuses every 3 years or every 15000 hours
(agehardening).
- Check that no water has penetrated into the control box.
Mechanical checks
- Check the tightening of the fan tower, fan, compressor and
control box fixing bolts.
control manual),
TM
Water circuit checks
- Check the water connections.
- Purge  the  water  circuit  (see  chapter  'Water  flow  control 
procedure').
- Clean the water filter (see chapter 'Water flow control
procedure').
- Check the operation of the flow switch.
- Check the status of the thermal piping insulation.
- Check the concentration of the anti-freeze protection solution
(ethylene glycol or polyethylene glycol).
Refrigerant circuit
- Fully clean the air evaporators with a low-pressure jet and a 
bio-degradable cleaner (counter-current cleaning - see
chapter 'Evaporator coil - level 2).
- Check the unit operating parameters and compare them with
previous values.
- Carry out an oil contamination test. Replace the oil, if
necessary.
- Check the operation of the high-pressure switches. Replace
them if there is a fault.
- Check the fouling of the filter drier. Replace it if necessary.
- Keep and maintain a maintenance sheet, attached to the
unit..
All these operations require strict observation of adequate safety
measures: individual protection garments, compliance with all
industry regulations, compliance with applicable local
regulations and using common sense.

15.3 - Level 3 (or higher) maintenance

The  maintenance  at  this  level  requires  specific  skills/approval/ 
tools and know-how and only the manufacturer, his representative
or authorised agent are permitted to carry out these operations.
These maintenance operations concern for example:
- a major component replacement (compressor, condenser),
- any intervention on the refrigerant circuit (handling
refrigerant),
- changing of parameters set at the factory (application
change),
- removal or dismantling of the unit,
- any intervention due to a missed established maintenance
operation,
- any intervention covered by the warranty.
To reduce waste, the refrigerant and the oil must be transferred
in accordance with applicable regulations, using methods
that limit refrigerant leaks and pressure drops and with
materials that are suitable for the products.
Any detected leaks must be repaired immediately.
The compressor oil that is recovered during maintenance
contains refrigerant and must be treated accordingly.
Refrigerant under pressure must not be purged to the open
air.
If a refrigerant circuit is opened, plug all openings, if the
operation takes up to one day, or for longer periods charge
the circuit with nitrogen.
NOTE: Any deviation or non-observation of these maintenance
criteria will render the guarantee conditions for the unit nul
and void, and the manufacturer, Carrier SCS, will no longer
be held responsible.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents