Nominal System Water Flow Control; General; Water Flow Control Procedure (Fixed Speed) - Carrier AquaSnap 61AF 022 Installation, Operation And Maintenance Instructions

High-temperature heat pumps
Table of Contents

Advertisement

9 - NOMINAL SYSTEM WATER FLOW CONTROL

9.1 - General

The optional water circulation pumps of the 61AF units have been
sized to allow the hydraulic modules to cover all possible
configurations based on the specific installation conditions, i.e. for 
various  temperature  differences  between  the  entering  and  the 
leaving water (ΔT) at full load, which can vary between 3 and 10 
K. This required difference between the entering and leaving water 
temperature determines the nominal system flow rate.
The pump of the hydraulic module is a variable speed pump. Two
different water flow control can be selected:
- fixed speed control
- variable speed control based on constant temperature
difference.
Default factory setting is fixed speed. Settings change need to be 
done by a Carrier Service representant.
For both flow control and for energy saving, the speed of the pump 
will be reduced to its minimum when unit capacity is 0%.
It is essential to know the nominal system flow rate to be able to 
control it, using the variable pump speed or a manual valve that
must be on the water leaving piping of the system (item 20 in the
typical hydraulic circuit diagram).
The flow control with the pump speed or with the valve permits 
adjustment of the pressure/system flow rate curve in accordance 
with the pump pressure/flow rate curve to obtain the nominal flow 
rate at the required operating point (see example for unit size
61AF 035). The pressure drop reading in the plate heat exchanger
is used as means of control and adjustment of the nominal system 
flow rate. This reading can be taken with a differential pressure 
gauge that must be installed at the heat exchanger inlet and outlet.
Use the specifications of the unit selection to know the system 
operating conditions and to deduce the nominal flow rate and the 
plate heat exchanger pressure drop at the specified conditions. If 
this information is not available at the system start-up, contact the
technical service department responsible for the installation to get
it.
These characteristics can be obtained with the Electronic
Catalogue selection program for all ΔT conditions in the range of 
3 to 10 K.
For domestic hot water applications (leaving water temperatures
above 60°C) the control cannot be made at a ΔT below 8 K at the 
condenser.

9.2 - Water flow control procedure (fixed speed)

Hydraulic circuit cleaning procedure
- Open the valve fully (item 20) if present.
- Start-up the system or unit pump (by quick test), if the unit is
equipped with a hydraulic module with a pump.
- Read the plate heat exchanger pressure drop by taking the
difference of the readings of the pressure gauge connected 
to the unit inlet and outlet (item 19).
- Let the pump run for two consecutive hours to clean the
system hydraulic circuit (presence of solid contaminants).
- Take another reading.
- Compare this value to the initial value.
- If the pressure drop has decreased, this indicates that the
screen filter must be removed and cleaned, as the hydraulic 
circuit contains solid particles. In this case close the shut-off 
valves at the water inlet and outlet (item 17) and remove the
screen filter (item 18 or 1 for a unit with hydraulic module) 
after emptying the hydraulic section of the unit (item 4).
- Purge the air from the circuit (items 10 and 15).
- Renew, if necessary, to ensure that the filter is not
contaminated.
Water flow control procedure
- When the circuit is cleaned, read the pressures at the
differential  pressure  gauge  (BPHE  leaving  water  pressure   
-BPHE entering water pressure), to find out the pressure drop 
for the plate heat exchanger and the internal piping.
- Compare the value obtained with the theoretical selection
value.
- If the pressure drop measured is higher than the value
specified this means that the unit flow rate (and thus system       
flow rate) is too high. The pump supplies an excessive flow 
rate based on the global pressure drop of the application. In
this case close the control valve or reduce the pump speed.
Read the new pressure difference.
- Proceed by successively closing the control valve or reducing
the pump speed until you obtain the specific pressure drop 
that corresponds to the nominal flow rate at the required unit 
operating point.
- Verify the minimum speed pump setting(when unit capacity
is 0%) is compatible with the flow switch protection (no flow 
switch alarm for minimum speed).
NOTE: If the system has an excessive pressure drop in
relation to the available static pressure provided by the
system pump the nominal water flow rate cannot be obtained
(the resulting flow rate is lower) and the temperature
difference between the condenser entering and leaving water
will increase.
To reduce the pressure drops of the hydraulic system, it is
necessary:
- to reduce the individual pressure drops as much as possible
(bends, level changes, accessories, etc.).
- to use a correctly sized piping diameter.
- to avoid hydraulic system extensions, wherever possible.
Example: 61AF 035 at Eurovent conditions of 1.76 l/s
20
2
16
12
8
4
1
4
0
0,5
1
1,5
Legend
1 
'BPHE pressure drop/flow rate'' curve
2
With the valve open or with the maximum pump speed, the pressure drop read
(18 kPa) gives point A on the curve.
A Operating point reached with the valve open / maximum pump speed.
3 
The flow rate achieved is 3.4 l/s: this is too high, and the valve must be closed 
or the pump speed decreased.
4
With valve is partially closed or speed decreased, the pressure drop read (6
kPa) gives point B on the curve.
B Operating point reached with the valve partially closed / pump speed reduced.
5 
The flow rate achieved is 1.76 l/s: this is the required flow rate and the settings               
are adequate
A
B
5
3
2,5
3
2
Water flow rate, l/s
3,5
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents