Chapter 2: Smoke control system hardware
Table 8: VAV smoke control settings
Smoke zone
Exhaust air damper OPEN
Supply air damper CLOSED
FSCS firefighter smoke
control station
The FSCS, where required, is most often located in the
building's fire command center. The FSCS is a remotely
networked panel, which also contains an FSCS series
graphic annunciator. Where the fire command center is
also located in the building's central security center, an
SCS with a graphic annunciator may also serve as the
FSCS.
The FSCS series graphic annunciator, with network
support hardware, is capable of providing both
monitoring and manual control of smoke control system
components. The graphic annunciator, when combined
to the correct Signature Series modules, can be used by
firefighters to start and stop fans and open and close
dampers for smoke control. The system, while designed
primarily for occupant protection and egress, can be
used by firefighters to exhaust smoke and allow for
effective fire attack and extinguishment by manual
means.
VM-1 SCS
Smoke control systems, which are not interconnected as
part of an VM-1 fire alarm network panel, constitute a
stand-alone system. The descriptions of components
which follow address a stand-alone smoke control
system, but can also be applied to a FACP function with
the smoke control system components sharing common
inputs and hardware in the VM-1 fire alarm network
panel.
36
Adjacent zones
Exhaust air damper CLOSED
Supply air damper OPEN
Terminal unit discharge
damper OPEN
Central VAV system
Supply fan ON
Return fan ON
Exhaust air damper OPEN
Outside air damper OPEN
Return air damper CLOSED
Reset static pressure control to
maximize air flow and prevent duct
failure
Table 9: VM-1 components
Model
CAB6B
VMD(G/R)
VM-CPU
C-CPUD
VM-LCD
PS10-4B
VM-NOC
VM-NOCF
VM-ETH1
VM-DACT
VM-SLCXB
CLA-PS10
D12LS-VM
VMI-PMI
VM-MFK
ACHS
CDR-3
RPM
CTM
GCI
GCI-NB
GCIX
Remote zones on same central system
Exhaust air damper CLOSED
Supply air damper CLOSED
Description
Control panel back box
Control panel door
CPU main board and dual loop controller
CPU daughter card
LCD user interface
Power supply
Network option card, RS-485, 8 nodes, max.
Network option card, fiber optic, 8 nodes, max.
Ethernet adapter card
Dual line dialer
Signaling line loop controller expansion card
Class A NAC adapter card
Annunciator strip with 12 LED-switch groups.
Each group consists of one switch and one
programmable LED (amber, red, blue, or green)
over an amber LED
Paging microphone interface
Firefighter's telephone kit
Audio channel selector cards
Coder module
Reverse polarity module
City tie module
Graphic annunciator interface card
Graphic annunciator interface card
Graphic annunciator expander card
VM-1 Smoke Management Application Guide