Chapter 3: Smoke control system programming
Name:
EXHAUST FAN INTERLOCK - CORR 3
Inputs:
Monitor, ZONE_1_EXH_DAMPR_OPEN_RELAY
Outputs:
ON, Low, Both, EXHAUST_FAN_ON_RELAY
OFF, Low, Both, EXHAUST_FAN_OFF_RELAY
Name:
EXHAUST FAN INTERLOCK – CORR 4
Inputs:
Monitor, EXHAUST_FAN_OFF_RELAY
Outputs:
OFF, Low, Both,
ZONE_1_EXH_DAMPR_OPEN_RELAY
ON, Low, Both,
ZONE_1_EXH_DAMPR_OPEN_RELAY
Indicating fan and damper status
The FSCS is required to provide LEDs for indicating fan
and damper status. Typically, the LEDs are disabled
until the FSCS has control of the smoke control system.
The correlation inputs and outputs shown below can be
used to create correlations that demonstrate how to
program fan and damper status indicators.
Name:
FSCS STATUS LEDS - CORR 1
Inputs:
Startup
Outputs:
Disable, Low, Both, FSCS_SW/LED_STRIP_2
FSCS STATUS LEDS - CORR 2
Name:
Inputs:
Alarm, <all smoke control smoke
detectors>
Outputs:
Enable, Low, Both, FSCS_SW/LED_STRIP_2
44
Name:
FSCS STATUS LEDS - CORR 3
Inputs:
Monitor, SUPPLY_DAMPER_OPEN_RELAY
Outputs:
Steady, Low, Both, SUPPLY_DAMPER_OPEN_LED
Name:
FSCS STATUS LEDS - CORR 4
Inputs:
Trouble, SUPPLY_DAMPER_OPEN_RELAY
Outputs:
Steady, Low, Both, SUPPLY_DAMPER_TRBL_LED
Name:
FSCS STATUS LEDS - CORR 5
Inputs:
Monitor, SUPPLY_DAMPER_CLOSE_RELAY
Outputs:
Steady, Low, Both,
SUPPLY_DAMPER_CLOSE_LED
Name:
FSCS STATUS LEDS - CORR 6
Inputs:
Trouble, SUPPLY_DAMPER_CLOSE_RELAY
Outputs:
Steady, Low, Both, SUPPLY_DAMPER_TRBL_LED
Steady, Low, Both, SUPPLY_DAMPER_TRBL_LED
Name:
FSCS STATUS LEDS - CORR 7
Inputs:
Monitor, SUPPLY_FAN_ON_RELAY
Outputs:
Steady, Low, Both, SUPPLY_FAN_ON_LED
FSCS STATUS LEDS - CORR 8
Name:
Inputs:
Trouble, SUPPLY_FAN_ON_RELAY
Outputs:
Steady, Low, Both, SUPPLY_FAN_TRBL_LED
VM-1 Smoke Management Application Guide