Kidde VM-1 Manual page 57

Hide thumbs Also See for VM-1:
Table of Contents

Advertisement

The operational testing of each individual building
system component is performed to determine if smoke
zones or areas are complete exclusive of VM-1 SCS
programmed commands. These operational tests
normally will be performed by various trades before
interconnection to the VM-1 SCS is made.
It should be certified in writing by the responsible trades
that each system component's installation is complete
and the component is functional including relays
installed by others for interconnection to the VM-1 SCS.
Each component test should be individually
documented, including such items as speed, voltage,
and amperage.
Because smoke control systems are usually an integral
part of building operating systems, testing of the building
system should include the following subsystems to the
extent that they affect the operation of the smoke control
system:
Energy management system
Building management and security system
HVAC equipment
Electrical equipment
Temperature control system
Power sources and standby power for fans and
damper
Automatic suppression systems
Automatic operating doors and closures
Emergency elevator operation
In most applications building control components to the
smoke control system are required to operate from the
building's emergency power system as a backup to
primary power. The electrical load required for motors in
fan control circuits and status indicators from the
emergency power must be provided for in emergency
power design.
VM-1 SCS/FSCS component testing: Components
activated by the smoke control system to be tested
include:
Dedicated smoke control systems
Nondedicated smoke control systems
Fire alarm systems installed under NFPA 72
VM-1 Smoke Management Application Guide
Chapter 4: Smoke control acceptance and testing
The FSCS series graphic annunciator must receive
power from other sources. The cabinet does not contain
batteries for emergency power.
Acceptance testing
The intent of acceptance testing is to demonstrate that
the final integrated system installation complies with the
specified design and is functioning properly. One or
more of the following should be present to grant
acceptance:
Building system designer
VM-1 SCS designer/installer
AHJ
All documentation from component testing should be
available for inspection.
Building test equipment
The following equipment may be needed to determine
air flows and compartmentation as a part of smoke
control acceptance testing:
Differential pressure gauges, inclined water or
electronic manometer
Scale suitable for measuring door-opening force
Anemometer, including traversing equipment
Ammeter
Flow-measuring hood (optional)
Door wedges
Tissue paper roll (for indicating direction of airflow)
Signs indicating a test of the smoke control system
is in progress
Walkie-talkie radios for coordinating equipment
VM-1 SCS test equipment
Required Tools:
Slotted screwdriver, insulated
Digital multimeter
12 in. (30.5 cm) jumper lead with alligator clips
Panel door key
53

Advertisement

Table of Contents
loading

Table of Contents