Kidde VM-1 Manual page 59

Hide thumbs Also See for VM-1:
Table of Contents

Advertisement

Initial acceptance testing for CPU panel controller
module with LCD display module
1. Verify the CPU is properly installed on the chassis
and its mounting plungers securely in place, and that
the LCD is properly installed on the CPU and its
mounting screws tightened. Verify that removable
terminal strips TB1 and TB2 are firmly seated.
2. Verify that all components are installed in
workmanlike manner.
3. Verify that the correct date and time are displayed
on the LCD display, and the Power LED is on.
4. Activate the lamp test function: Main Menu > Test >
Lamp Test. Verify that all LEDs on the graphic panel
light.
5. Initiate an alarm. Verify that the Alarm LED flashes,
the alarm relay transfers, the correct device
message appears at the top of the LCD window, the
active point counter increments, the event sequence
indicates a 1, the active Alarm events counter at the
bottom of the display indicates 0001, the event type
indicates Alarm, and the local panel buzzer sounds.
The graphic annunciator panel alarm LED and zone
LED will light, also.
Access Main Menu > Test > VM Device Test >
Alarm, and enter a panel, card, and device address.
Verify that the Alarm LED flashes.
Press the ACK/Panel Silence button. Verify that the
panel buzzer silences, the ACK/Panel Silence LED
lights, and the Alarm LED lights steady.
Press the Alarm Silence button. Verify that the
required notification appliances are silenced.
Press the Details button. Verify that the alarm
device's details message, if any, displays.
If a printer is connected to the CPU, verify that all
specified information appears on the printer.
6. Initiate a second alarm in another smoke control
zone. Verify that it appears at the bottom of the LCD
window, the active point counter changes, the event
sequence indicates a 2, the active Alarm events
counter at the bottom of the display indicates 0002,
the event type indicates alarm, the Alarm LED
flashes, the local panel buzzer sounds, and the first
alarm message remains at the top of the LCD
window.
VM-1 Smoke Management Application Guide
Chapter 4: Smoke control acceptance and testing
Press the ACK/Panel Silence button. Verify that the
Alarm LED lights steady.
7. Initiate a third alarm in a remaining area. Verify that
its message appears at the bottom of the LCD
window, the active point counter changes, the event
sequence indicates a 3, the active Alarm events
counter at the bottom of the display indicates 0003,
the event type indicates Alarm, the local panel
buzzer sounds, and the alarm message remains at
the top of the LCD window.
8. Use the up and down buttons to verify that you can
scroll through all three messages in the Alarm
queue, as indicated by the event sequence window.
9. Press the Reset button. Verify that all initiating
devices reset and that all panel indicators clear
except the green power LED on the panel or remote
annunciator CPU, and the graphic annunciator
panel.
10. Initiate an active monitor condition. Verify that the
Monitor LED flashes, the correct active monitor
device message appears in the top and bottom of
the LCD window, the active point counter changes,
the event sequence indicates a 1, the active Monitor
events counter at the bottom of the display indicates
M001, and the event type indicates Monitor.
Press the ACK/Panel Silence button. Verify that the
Monitor LED lights steady.
11. Initiate a second active monitor condition. Verify that
the first monitor message remains at the top of the
LCD window, the second monitor message appears
at the bottom of the window, the active point counter
changes, the event sequence indicates a 2, and the
active Monitor events counter at the bottom of the
window indicates 0002.
12. Initiate an active trouble condition. Verify that the
Trouble LED flashes, the correct active trouble
device message appears in the top and bottom of
the LCD window, the trouble relay transfers, the
active point counter changes, the event sequence
indicates a 1, the active Trouble events counter at
the bottom of the window indicates 0001, the event
type indicates Trouble, and the local panel buzzer
sounds. The graphic annunciator panel general
trouble LED will light, also.
55