Siemens SIMATIC NET RUGGEDCOM RS940GF Installation Manual page 43

Rugged
Table of Contents

Advertisement

Certification
6.2 EMC and Environmental Type Tests
61000-4-29
61000-4-11
61000-4-12
61000-4-16
61000-4-17
IEC 60255-5
IEEE 1613 (C37.90.x) EMC Immunity Type Tests
Note
The RUGGEDCOM RS940GF meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
34
Test
IEC
Voltage Dips and Interrupts
IEC
IEC
Damped Oscillatory
IEC
Mains Frequency Voltage
IEC
Ripple on DC Power Supply
Dielectric Strength
HV Impulse
IEEE Test
C37.90.3
ESD
C37.90.2
Radiated RFI
C37.90.1
Fast Transient
Description
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
DC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Test Levels
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
30% for 1 period,
60% for 50 periods
100% for 5 periods,
100% for 50 periods
2.5 kV common, 1 kV
differential mode @ 1 MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
30 V Continuous,
300 V for 1 s
30 V Continuous,
300 V for 1 s
10%
2 kVAC  (Fail-
Safe Relay output)
2 kV
2 kV
5 kV  (Fail-Safe
Relay Output)
5 kV
5 kV
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
Installation Manual, 01/2021, C79000-G8976-1356-04
Severity
Levels
 
 
 
3
3
3
4
4
3
 
 
 
 
 
 
RUGGEDCOM RS940GF