ABOUT THE CONTROLLER

The MFWC controller enables efficient use and operational control of the mixer system. For each of the single setting
procedures, the keys are assigned to specific functions and explained.
The controller menu contains key words for the measured values and settings, as well as help texts and graphs.
Main features of the MFWC controller:
- Backlit display showing text and graphic content
- Simple viewing of current measurement values
- Analysis and monitoring of the system by means of statistical graphs, etc.
- Extensive setting menus with explanations
- Menu lock: activated to prevent unintentional alteration of settings
- Function allowing restoration of previously selected values or factory settings
- Wide range of additional functions.
DISPOSAL
The unit conforms to the European RoHS directive 2011/65/EU for the restriction of the use of certain hazardous substanc-
es in electrical and electronic equipment.
b
The unit must not under any circumstances be disposed of with ordinary household refuse. Dispose of the unit only
at appropriate collection points or ship it back to the seller or manufacturer.
TECHNICAL SPECIFICATIONS
Electrical specifications
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100-230VAC
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 - 60Hz
Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5W – 2.5W
- electromechanical relays R1-R3 . . . . . . . . . . . . . . . . . . . . . . . . 460VA for AC1 / 460W for AC3
- PMV output freq. 10kHz 10V . . . . . . . . . . . . . . . . . . . . . . . . . . . for 10 kΩ load
Internal fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T2A / 250V slow-blow
Ingress protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP40
Protection class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 x Pt1000 + 2 x VFS (vortex flow sensors)
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PT 1000 -40°C up to 300°C
Vortex flow sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0°C to 100°C (-25°C /120°C short term)
1 l/min - 12 l/min (VFS1-12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-0.6 bar
1 l/min – 20 l/min (VFS1-20) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-1 bar
2 l/min - 40 l/min (VFS2-40) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-1.6 bar
5 l/min - 100 l/min (VFS5-100) . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-2.5 bar
10 l/min – 200 l/min (VFS10-200) . . . . . . . . . . . . . . . . . . . . . . . . . 0-4 bar
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-6 bar
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-10 bar
Permissible cable length of sensors and appliances
other PT1000 sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <10m
VFS/RPS Sensoren . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <3m
CAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <3m
PWM / 0...10V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <3m
mechanichal relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <10m
Real Time Clock
RTC with 24 hour power reserve
Permissible ambient conditions
Ambient temperature:
- for controller operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0°C÷40°C
- for transport/storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0°C÷60°C
Air humidity:
- for controller operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . max. 85% relative humidity at 25 °C
- for transport/storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . no moisture condensation permitted