6.3.3 Setting central addresses, unit names and tenant numbers

Use this screen to set central addresses, names of units connected to the system and tenant
numbers.
Procedure
Select 5.Initial settings in the main menu and 2.CNTR/Unit/Ten. No. in the sub menu, then
proceed as follows.
1.Status/Control
2.Total data/Cut-off
3.Distrib. ratio/Usage
4.Maintenance/Test Run
5.Initial settings
6.Auxiliary settings
A
A When you touch a central address column, a screen will be displayed as shown on the right.
Input a number 1 to 64 to set central address.
When you touch [Auto], the central address will be automatically set.
Two identical central address settings cannot be used within a link system. If you input an existing
address, the input data is cancelled.
It may take several minutes before the central address settings are refl ected in the display.
When other central controllers (system controller, etc.) are connected, it is recommended to set the
central addresses on those units.