Srflt-Sscram Alarm - Alcatel-Lucent 1677 SONET Maintenance And Trouble Clearing

Hide thumbs Also See for 1677 SONET:
Table of Contents

Advertisement

3EM13853AF
Issue 01, September 2007
TAP-141

SRFLT-SSCRAM Alarm

PURPOSE
This procedure provides instructions to clear a SRFLT-SSCRAM alarm against a SSC card.
GENERAL
SRFLT-SSCRAM indicates system resource fault - the alarmed module is equipped with smaller
RAM size than its mate.
For information on TL1 command syntax, refer to the 1677 SONET Link Commands and Messages
manual (PN 3EM13852AF).
STEP
PROCEDURE
1
DANGER: Possibility of personal injury. Modules can be installed or removed with
rack power on. Hazardous electrical potentials are present; use extreme care when
installing or removing modules with power on.
WARNING: Possibility of equipment damage. Modules contain electrostatic-
2
sensitive devices (ESDs). These devices can be damaged by static discharge.
Refer to
Enter
3
Observe output. Note module with SRFLT-SSCRAM alarm.
4
Replace SSC card with SRFLT-SSCRAM alarm. Ensure the replacement SSC has the
5
same RAM size as the non-alarmed SSC. Refer to
procedures.
Enter
6
Did SRFLT-SSCRAM clear?
7
Contact next level of technical support for assistance.
8
9
STOP. This procedure is complete.
SRFLT-SSCRAM Alarm
Introduction
for special handling instructions.
and
RTRV-ALM-ALL;
RTRV-COND-ALL;
and
RTRV-ALM-ALL;
RTRV-COND-ALL;
If yes, go to step 9.
If no, go to step 8.
to retrieve all alarms and conditions.
IXL-103
for card replacement
TAP-141
4-103