Electrical Specifications H**A - Bard H42A1 Manual

Wall mounted package air conditioners
Table of Contents

Advertisement

Electrical Specifications — H**A Series
Rated
Volts
Model
and
Phase
Circuits
H42A1 - A00, A0Z
A05
A10
230/208-1
A15
A20
H42A1 - B00, B0Z
B09
230/208-3
B15
B18
H42A1 - C00, C0Z
C09
460-3
C15
H48A1 - A00, A0Z
A05
A10
230/208-1
A15
A20
H48A1- B00, B0Z
B09
230/208-3
B15
B18
H48A1 - C00, C0Z
C09
460-3
C15
H60A1 - A00, A0Z
A05
A10
230/208-1
A15
A20
H60A1 - B00, B0Z
B09
230/208-3
B15
B18
H60A1 - C00, C0Z
C09
460-3
C15
 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version),
Article 310 for power conductor sizing.
caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310
regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
* Top outlet supply option is available only factory installed and only on the selected models.
imPOrtant: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in
accordance with the National Electrical Code and all local codes.
Manual 2100-568A
Page
18 of 23
single circuit
No.
 Maximum
Field
Minimum
External
Power
Circuit
Fuse
Ampacity
or Ckt. Brkr.
1
33
50
1
33
50
1
59
60
1 or 2
85
90
1 or 2
111
125
1
25
35
1
34
35
1
53
60
2
N/A
N/A
1
13
15
1
18
20
1
27
30
1
37
50
1
37
50
1
59
60
1 or 2
85
90
1 or 2
111
125
1
29
40
1
34
40
1
52
60
2
N/A
N/A
1
14
20
1
18
20
1
27
30
1
41
60
1
41
60
1
59
60
1 or 2
85
90
1 or 2
111
125
1
28
40
1
34
40
1
53
60
2
N/A
N/A
1
15
20
1
18
20
1
27
30
table 3
 Minimum
 Field
Circuit
Power
Ground
Ampacity
Wire
Wire
Size
Ckt. A
Ckt. B
8
10
8
10
6
10
4
8
59
26
2
6
59
52
8
10
8
10
6
10
N/A
N/A
34
28
14
14
12
12
10
10
8
10
8
10
6
10
4
8
59
26
2
6
59
52
8
10
8
10
6
10
N/A
N/A
34
28
12
12
12
12
10
10
8
10
8
10
6
10
4
8
59
26
2
6
59
52
8
10
8
10
6
10
N/A
N/A
34
28
12
12
12
12
10
10
dual circuit
 Maximum
 Field
External Fuse
Power
or Ckt. Brkr.
Wire Size
Ckt. A
Ckt. B
Ckt. A
Ckt. B
60
30
6
10
60
60
6
6
35
30
8
10
60
30
6
10
60
60
6
6
40
30
8
10
60
30
6
10
60
60
6
6
40
30
8
10
 Ground
Wire Size
Ckt. A
Ckt. B
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

H42l1H48a1H48l1H60a1H60l1

Table of Contents