Figure 8 Fan Blade Setting; Troubleshooting; Fan Blade Setting Dimensions; Refrigerant Charge - Bard H42A1 Manual

Wall mounted package air conditioners
Table of Contents

Advertisement

trOubleshOOtinG

fan blade settinG dimensiOns

Shown in Figure 8 is the correct fan blade setting for
proper air delivery across the outdoor coil. Refer to
Table 1 for unit specific dimension.
Any service work requiring removal or adjustment
in the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.
fiGure 8
fan blade settinG
table 1
fan blade dimensiOn
model
H42A1 / H42L1
H48A1 / H48L1
H60A1 / H60L1
Manual 2100-568A
Page
16 of 23
MIS-1724
dimension
a
1.75"
r-410a

refriGerant charGe

This unit was charged at the factory with the quantity of
refrigerant listed on the serial plate. AHRI capacity and
efficiency ratings were determined by testing with this
refrigerant charge quantity.
The following pressure tables show nominal pressures
for the units. Since many installation specific situations
can affect the pressure readings, this information should
only be used by certified technicians as a guide for
evaluating proper system performance. They shall not
be used to adjust charge. If charge is in doubt, reclaim,
evacuate and recharge the unit to the serial plate charge.

remOVal Of fan shrOud

1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on
each side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser
and bottom. Nine (9) screws.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade, and shroud
assembly out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall.