Cooling Pressure - Bard H42A1 Manual

Wall mounted package air conditioners
Table of Contents

Advertisement

return air
model
temperature
75 deg. DB
62 deg. WB
80 deg. DB
h42a1/l1
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
h48a1/l1
67 deg. WB
85 deg. DB
72 deg. WB
75 deg. DB
62 deg. WB
80 deg. DB
h60a1/l1
67 deg. WB
85 deg. DB
72 deg. WB
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge
being in the system, the charge should be removed, system evacuated and recharged to serial plate charge weight.
NOTE:
Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check
condenser fan wiring. See "Condenser Fan Operation".
cOOlinG Pressure table
Pressure
75
80
Low Side
128
130
High Side
341
362
Low Side
137
139
High Side
350
371
Low Side
142
144
High Side
362
384
Low Side
125
127
High Side
349
370
Low Side
134
136
High Side
358
379
Low Side
139
141
High Side
371
392
Low Side
126
128
High Side
352
373
Low Side
135
137
High Side
361
383
Low Side
140
142
High Side
374
396
table 2
Air Temperature Entering Outdoor Coil °F
85
90
95
132
133
135
383
406
429
141
142
142
393
416
435
146
147
149
407
431
455
129
131
133
391
415
440
138
140
142
401
426
454
143
145
147
415
441
467
130
132
133
396
418
442
139
141
142
406
429
453
144
146
147
420
444
469
100
105
110
115
137
138
140
453
480
506
146
148
150
465
492
519
151
153
155
481
509
537
136
137
140
467
495
526
145
147
150
479
508
539
150
152
155
496
526
558
135
137
137
466
491
517
144
146
147
478
504
530
149
151
152
495
522
549
Manual 2100-568A
Page
120
142
144
534
564
152
154
548
578
157
159
567
598
143
146
557
590
153
156
571
605
158
161
591
626
139
141
544
571
149
151
558
586
154
156
578
607
17 of 23