Condensate drainage

The unit must be perfectly horizontal
in both directions. Connect the
condensate tray outlet (outer diam.
20 mm).
To ensure satisfactory condensate
drainage, the drainage tube must be
sloped 10°.There must not be a
condensate trap anywhere on the
line. However a siphon can be
provided to prevent outside air being
drawn in by the indoor unit. If the pipe
passes through a room, insulate it to
prevent damage caused by
condensation. We recommend
polyethylene foam (6 mm thick).

Electrical connections

If access to the electric cabinet is
problematic, it can be moved a
maximum distance of 500 mm.
All wiring and earthing must comply
with local standards.
Caution
a) Check the electrical characteristics
on the unit's name plate. Make
sure the wiring corresponds to the
manufacturer's electrical diagram
and local standards.
b) Power up the units using one or
more lines protected by a
disconnect switch and fuses.
c) Earth each unit.
d) The wires must not touch the
refrigerant lines, the motors or
other moving parts.
8
Installation
Condensate pump (accessory)
If it is not possible to drain the
condensates by gravity, a
condensate pump can be installed as
an accessory .
Figure 4 : Connection of the condensate drain
e) The manufacturer does not
assume any liability for problems
caused by modifications to the
unit's internal wiring.
f) Tighten the terminals securely.
Figure 5 : Moving the electric cabinet
It can lift the condensates a
maximum of 500 mm. For installation
and connection of the condensate
pump, refer to the submittals
supplied with this accessory.