16.5.3 Idle time during end position guiding
In closed-loop operation, the actuator's positioner must be operated with absolute travel ad-
justment (default setting).
Change the travel adjustment in the 'Settings' folder (Actuator\Travel).
Settings\Actuator\Functions
Function
Idle time during end position guiding
Note
The further description refers to the operation with absolute travel adjustment, unless speci-
fied otherwise.
16.5.4 Velocity
The actuator stem moves to the position determined by the input signal at the selected strok-
ing speed. There are three speed levels:
− Slow
=
− Standard =
− Fast
= 0.55 mm/s
Settings\Actuator\Travel
Function
Velocity
Note
The transit time is calculated from the travel and the stroking speed. The transit time is the
time that the actuator stem needs to move through the adjusted travel.
The following applies:
EB 5857 EN
0.2 mm/s
0.3 mm/s
Annex A (configuration instructions)
WE
0 s
WE
Standard
Transit time in s =
Adjustment range
0 to 99 s
Adjustment range
Slow, Standard, Fast
Travel in mm
Stroking speed in mm/s
16-7