16.5 Travel

16.5.1 Limited travel range

The Limited travel range parameter determines in % how far the actuator stem can move at
the maximum. The travel determined during initialization acts as the reference.
Settings\Actuator\Travel
Function
Limited travel range

16.5.2 Travel adjustment

Travel adjustment can be made to be absolute or relative. The way the travel adjustment is
made affects the control behavior.
− Absolute travel adjustment:
The absolute travel adjustment causes the actuator stem to move to the travel position de-
termined by the input signal. To achieve this, an automatic zero calibration is performed
after every start-up to obtain a reference value for the zero point. The position feedback
indicates the position of the actuator stem.
− Relative travel adjustment
The relative travel adjustment causes the change in input signal to be reproduced by the
position of the actuator stem. The actuator stem extends or retracts from the current actu-
ator stem position corresponding to the change in signal. After starting up the actuator, a
zero calibration is not performed. The stem position is unknown on reconnection after
power failure. The input signal is assigned in this case as the start value. 12 V is issued
as the position feedback signal. When, during operation, the actuator stem reaches the
travel stop for "stem extends" and, at the same time, the input signal is 0 %, the stem po-
sition is recognized as a result.
Settings\Actuator\Travel
Function
Limited travel range
Tip
In closed-loop operation, the positioner must be operated with absolute travel adjustment
(default setting).
16-6
WE
Adjustment range
100.0 %
30.0 to 100.0 %
WE
Adjustment range
100.0 %
30.0 to 100.0 %