Settings\Actuator\Blockage
Function
Blockage removal

16.4.3 Indicate blockage

The positioner indicates a blockage when the Indicate blockage function is active (only when
the 'Blockage detection' is activated).
− 12 V is issued at the output as position feedback signal.
Settings\Actuator\Blockage
Function
Indicate blockage

16.4.4 Blocking protection

The Blocking protection prevents the valve from seizing up. If the actuator stem is in the 0 %
position, it is extended slightly and then moved back to the closed position 24 hours after it
last moved.
Movement of the actuator stem caused by the activated blocking protection is indicated by
the yellow LED:
− Protecting against blockage
Settings\Actuator\Blockage
Function
Blocking protection