2.3 Programming
(Example 2) Program example 2
This is an examinable program that takes the difference of the AD368 input with the
previous input,magnifies it (x2), and outputs from DA374. The 4 to 20 mA mode is
assumed for AD368.
2
Code a routine to "set the disconnect error flag and set the input to 0 when
disconnect is detected" prior to the above routine because the 4 to 20 mA mode of
the AD368 has a disconnect detection function.
In this example, Declared 'OPEN-ERR' as global variables,Addition to I/O Variable
Also, declare the previous value as a static variable because it must be retained
internally.
Program
67
6F8C0869