Toshiba V Series User Manual page 63

Analog module
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

Special
functions
External power supply
Current
consumption
Weight
(2) Individual Specification
type
DA314S
DA324S
DA364S
DA374S
6F8C0869
Item
Error
(a)Output HOLD / CLEAR mode
detection
(b)External 24Vdc power supply
voltage drop error detection.
(c)Each channels power supply
voltage drop error detection.
Alarm output
Contact output 24Vdc, 0.5A
(Normal close)
24 Vdc ± 10 %
Internal
350 mA (5 Vdc)
External
300 mA (24 Vdc)
400 g
Maximum
Output range
output
0 to +5V
+5.12V (typ)
0 to +20mA
+20.48mA
(typ)
± 10.24V (typ)
-10 to +10V
0 to +10V
± 5.12V (typ)
-5 to +5V
0 to +5V
± 20.48mA
-20 to +20mA
0 to +20mA
(typ)
± 10.24mA
-10 to +10mA
0 to +10mA
(typ)
1.5 DA314S/DA324S/DA364S/DA374S
Specification
Load impedance
range
Output rang is fixed
500
or more
Output rang is fixed
550
or less
Voltage output range,Uni/
1k
or more
Bi,16bit/12bit,selectabl DIP
switch setting (voltage output
500
or more
only)
current output range,Uni/
550
or less
Bi,16bit/12bit,selectabl DIP
switch setting (current output
1.1k
or less
only)
Uni : unipolar
Bi : bipolar
Remarks
Remarks
51