Insert an insulation amplifier between each sensor if there is a difference in potential
between sensors (difference in common potential) because there is no insulation
between each channel of this module.
Sensor A
Potential difference
Sensor B
If measurement values are unstable due to noise influences, change the grounding for
the shield in the following order and select the most stable method.
(1) Ground at sensor side
(2) Ground to sensor side common
Insulation amplifier
External wire
External wire
External wire
Internal circuit
Internal circuit
Internal circuit
model 3000 Analog module User's Manual