Siemens RUGGEDCOM RX1100P Installation Manual page 49

Table of Contents

Advertisement

RUGGEDCOM RX1100P
Installation Guide
Test
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
a
Siemens-specified severity levels
b
Only applicable to functional earth connections separated from the safety earth connection.
IEEE 1613 (C37.90.x) EMI Immunity Type Tests
NOTE
The RX1100P meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for
copper ports.
Test
IEEE C37.90.3
C37.90.2
IEEE C37.90.1
EMI and Environmental Type Tests
Description
Damped Oscillatory
Mains Frequency Voltage
Ripple on DC
Power Supply
Dielectric Strength
HV Impulse
ESD
Radiated RFI
Fast Transient
Oscillatory
Signal ports
2.5 kV common,
1 kV differential
mode @ 1 MHz
DC Power ports
2.5kV common,1kV
mode @ 1 MHz
AC Power ports
2.5 kV common,
1 kV differential
mode @ 1 MHz
Signal ports
30 V Continuous,
DC Power ports
30 V Continuous,
DC Power ports
Signal ports
2 kVAC (Fail-
Safe Relay output)
DC Power ports
AC Power ports
Signal ports
5 kV (Fail-Safe
DC Power ports
AC Power ports
Description
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
Test Levels
Severity Levels
differential
300 V for 1 s
300 V for 1 s
10%
1.5 kVDC
2 kVAC
Relay output)
5 kV
5 kV
Test Levels
+/- 8 kV
+/- 15 kV
35 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV
+/- 4 kV
2.5 kV common mode @ 1 MHz
2.5 kV common and
differential mode @ 1 MHz
Chapter 6
Certification
3
3
3
4
4
3
43

Advertisement

Table of Contents
loading