Endress+Hauser HART Levelflex M FMP43 Operating Instructions Manual

Guided level-radar
Hide thumbs Also See for HART Levelflex M FMP43:

Advertisement

Quick Links

Operating Instructions
Levelflex M FMP43
Guided Level-Radar
HART/4 to 20 mA
6
BA357F/00/en/07.07
No. 71040912
Valid as of software version
V 01.04.02

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser HART Levelflex M FMP43

  • Page 1 Operating Instructions Levelflex M FMP43 Guided Level-Radar HART/4 to 20 mA BA357F/00/en/07.07 No. 71040912 Valid as of software version V 01.04.02...
  • Page 2 Brief overview Levelflex M FMP43 with HART/4...20 mA Brief overview For quick and simple commissioning: → ä 6 Safety instructions Explanation of the warning symbols You can find special instructions at the appropriate position in the chapter in question. The positions are indicated with the icons Warning #, Caution " and Note ! Æ...
  • Page 3 Levelflex M FMP43 with HART/4...20 mA Brief overview Brief operating instructions Levelflex M - Brief operating instructions KA189F/00/a2/03.07 52012501 Contrast: measured value dist./ meas value Group selection process empty check start basic setup tank medium full dist./ range of properties property cond.
  • Page 4 Brief overview Levelflex M FMP43 with HART/4...20 mA Endress + Hauser...
  • Page 5: Table Of Contents

    Installation ..... 12 Contact addresses of Endress+Hauser ... 80 Incoming acceptance, transport, storage ..12 Technical data .
  • Page 6: Safety Instructions

    Safety instructions Levelflex M FMP43 with HART/4...20 mA Safety instructions Designated use The Levelflex M FMP43 is a compact level transmitter for continuous measurement in liquids, using the guided level radar/TDR: time domain reflectometry measuring principle. Installation, commissioning and operation The Level M is designed to meet state-of-the-art safety requirements and conforms to applicable standards and EC regulations.
  • Page 7: Notes On Safety Conventions And Icons

    Levelflex M FMP43 with HART/4...20 mA Safety instructions Notes on safety conventions and icons In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding symbol in the margin. Safety instructions Warning! Indicates...
  • Page 8: Identification

    2.1.1 Nameplate The following technical data are given on the device nameplate: Order No Designation according to Directive 94/9/EC (see Order Information) and designation of protection ENDRESS+HAUSER Made in Germany Serial number LEVELFLEX-M D-79689 Maulburg Order Code: Ser.-No.: IP68 / NEMA 6P...
  • Page 9 Levelflex M FMP43 with HART/4...20 mA Identification O-ring Material; Temperature: EPDM, FDA, USP Cl. VI; - 20 °C to 130 °C Kalrez, FDA, USP Cl. VI; - 20 °C to 150 °C Special version, to be specified Process Connection: -- Threaded boss -- Thread M24, 316L, install >...
  • Page 10 Identification Levelflex M FMP43 with HART/4...20 mA Additional Option: A Basic version EN 10204-3.1 material (316L wetted parts) inspection certificate *CoC, EN 10204-3.1 material (316L wetted parts) inspection certificate Special version, to be specified FMP43- Complete product designation ⇓ Please enter probe length in mm or inch / 0.1 inch inch / 0.1 inch Probe length LN →...
  • Page 11: Scope Of Delivery

    The device takes into account applicable standards and regulations which are listed in the EC declaration of conformity and thus meets the legal requirements of the EC Directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 12: Installation

    Installation Levelflex M FMP43 with HART/4...20 mA Installation Incoming acceptance, transport, storage 3.1.1 Incoming acceptance Check the packing and contents for any signs of damage. Check the shipment, make sure nothing is missing and that the scope of supply matches your order. 3.1.2 Transport "...
  • Page 13: Installation Conditions

    Installation Installation conditions 3.2.1 Dimensions Housing (see feature 80 in "Ordering information") - dimensions and materials Dimensions for the process connection and the probe type → ä 14. max. 110 ENDRESS+HAUSER F12 housing (Aluminium) L00-F12xxxx-06-00-00-en-001 max. 100 ENDRESS+HAUSER T12 housing...
  • Page 14 Installation Levelflex M FMP43 with HART/4...20 mA Probes (see Feature 70 in "Ordering information") - Dimensions and materials F12 / T12 / F23 housing option “6/7”: remote electronic reference point of measurement 4 x Ø 8,5 Ø 5 option “5”: compact, detachable option “1”: compact...
  • Page 15 Levelflex M FMP43 with HART/4...20 mA Installation Process connections (see Feature 40 in "Ordering information") - Dimensions and materials Process connection Designation Versions Approvals Option Tri-clamp ISO2852 DN25-38 (1 to 1-½")* = 16 bar 43,4 Ø 50,4 Tri-clamp ISO2852 • 5 DN40-51 (2")* (certificate pending) = 16 bar...
  • Page 16 Installation Levelflex M FMP43 with HART/4...20 mA Process connection Designation Versions Approvals Option DIN11851 DN40 PN40 with slotted nut F40* = 16 bar Ø 56 Ø 39 • 0.8 μm DIN11851 DN50 PN40 with slotted nut F50* = 16 bar Ø...
  • Page 17 Levelflex M FMP43 with HART/4...20 mA Installation Process connection Designation Versions Approvals Option Thread M24 x 1.5 Accessory: weld-in adapter Weld-in adapter • 0.8 μm order number: 71041381 = 16 bar Ø 65 All metal parts used in the process in 316L (1.4435) Endress + Hauser...
  • Page 18: Installation Instructions

    Installation Levelflex M FMP43 with HART/4...20 mA Installation instructions 3.3.1 Mounting tools A 4 mm Allen key is needed to turn the housing. 3.3.2 General instructions Normally use rod probes. Rope probes are used for measuring ranges > 4m and with restricted ceiling clearance which does not allow the installation of rigid probes.
  • Page 19 Levelflex M FMP43 with HART/4...20 mA Installation 3.3.3 Special instructions When installing in tanks with agitator, observe the lateral loading capacity of rod probes: • 10 Nm with 1.4435 / SS316L • 16 Nm with Hasteloy C22 (on request). The formula for calculating the bending torque M impacting on the probe: M = c ·...
  • Page 20 Installation Levelflex M FMP43 with HART/4...20 mA The probe must be mounted opposite the agitator. If possible, check whether a non-contact process, ultrasonic or level-radar would be better suited, particularly if the agitator generates large mechanical loads on the probe. L00-FMP43xxx-17-00-00-xx-005 3.3.4 Notes on special installation situations...
  • Page 21 • The wall retainer can also be used for mounting in display panels. Please observe the dimensions on → ä 13 for the cutout. display plate wall ENDRESS+HAUSER Levelflex M 4 x Ø 8,5 Ø 5 ENDRESS+HAUSER Levelflex M pipe Ø...
  • Page 22: Post-Installation Check

    Installation Levelflex M FMP43 with HART/4...20 mA 3.3.6 Turning the housing After mounting, the housing can be turned 350° in order to ease access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position: •...
  • Page 23: Cleaning Of The Probe

    Levelflex M FMP43 with HART/4...20 mA Installation Cleaning of the probe 3.5.1 Cleaning of the probe in the tank Installation close to tank wall • By installing the probe close to the tank wall, the cleaning effect is improved in cases where a spray ball is used.
  • Page 24 Installation Levelflex M FMP43 with HART/4...20 mA 3.5.2 Cleaning of the probe outside of the tank The probe can be disassembled so it can be cleaned better. The disassembly requires the following tools: • Note! F12/F23/T12 vise with fiber braces (surface protection for the polished probe rod) •...
  • Page 25 Levelflex M FMP43 with HART/4...20 mA Installation Assembly of the probe The assembly is done in reversed order: • screw adapter o with 4.5 Nm on the probe rod p • screw the adapter into the container process connection together with the probe rod and tighten with 20 Nm •...
  • Page 26: Wiring

    " Before connection please note the following: ● The power supply must be identical to the data on the Caution! nameplate (1). ENDRESS+HAUSER Made in Germany LEVELFLEX-M D-79689 Maulburg ● Switch off power supply before connecting up the device. Order Code: Ser.-No.:...
  • Page 27 " Before connection please note the following: ● The power supply must be identical to the data on the nameplate (1). Caution! ENDRESS+HAUSER Made in Germany LEVELFLEX-M D-79689 Maulburg ● Switch off power supply before connecting up the device. Order Code: Ser.-No.:...
  • Page 28: Connecting The Measuring Unit

    Wiring Levelflex M FMP43 with HART/4...20 mA Connecting the measuring unit Terminal compartment Three housings are available: • Aluminum housing F12 with additionally sealed terminal compartment for: – standard – EEx ia • Aluminum housing T12 with separate terminal compartment for: –...
  • Page 29 Levelflex M FMP43 with HART/4...20 mA Wiring Cable entry Cable gland: M20x1.5 (for EEx d: cable entry only) Cable entry: G ½ or ½ NPT Supply voltage HART, 2-wire All the following voltages are terminal voltages directly at the device: Terminal voltage Current Communication...
  • Page 30 T12 housing, see ordering information on → ä 8 • this protection is achieved through other appropriate measures (external protection devices e.g. HAW262Z). 4.2.1 Connecting HART with Endress+Hauser RMA422 / RN221N - ToF Tool - Fieldtool Package...
  • Page 31: Recommended Connection

    Levelflex M FMP43 with HART/4...20 mA Wiring " Caution! If the HART communication resistor is not built into the supply unit and the HART interface is to be used, it is necessary to insert a communication resistor of 250 Ω into the 2-wire line. Recommended connection 4.3.1 Potential equalization...
  • Page 32: Operation

    Operation Levelflex M FMP43 with HART/4...20 mA Operation Quick operation guide ENDRESS + HAUSER – >3 s Return to basic setup tank shape medium property Group Selection Standard safety settings aluminium tank plastic tank linearisation bypass / pipe extended calibr. coax probe concrete wall Selection and configuration in Operation menu:...
  • Page 33 Levelflex M FMP43 with HART/4...20 mA Operation 5.1.1 General structure of the operating menu The operating menu is made up of two levels: • Function groups (00, 01, 03, …, 0C, 0D): The individual operating options of the device are split up roughly into different function groups. The function groups that are available include: "basic setup", "safety settings.", "output", "display", etc.
  • Page 34: Display And Operating Elements

    Operation Levelflex M FMP43 with HART/4...20 mA Display and operating elements Four lines with 20 characters per line. Display contrast adjustable through key combination. (liquid crystal display) Orde Orde Ser.- Ser.- r Code r Code No.: No.: sber surin sber surin eich eich...
  • Page 35 Levelflex M FMP43 with HART/4...20 mA Operation 5.2.2 Display symbols The following table describes the symbols that appear on the liquid crystal display: Symbol Meaning ALARM_SYMBOL This alarm symbol appears when the device is in an alarm condition. If the symbol flashes, this indicates a warning.
  • Page 36: Local Operation

    Operation Levelflex M FMP43 with HART/4...20 mA Local operation 5.3.1 Locking the configuration mode The Levelflex can be protected in two ways against unauthorized changing of device data, numerical values or factory settings: "unlock parameter" (0A4): A value <> 100 (e.g. 99) must be entered in "unlock parameter" (0A4) in the "diagnostics"...
  • Page 37 There is no need to change these parameters under normal circumstances and consequently, they are protected by a special code known only to the Endress+Hauser service organization. Please contact Endress+Hauser if you have any questions.
  • Page 38 Operation Levelflex M FMP43 with HART/4...20 mA 5.3.3 Factory settings (reset) " Caution! A reset sets the device back to the factory settings. This can lead to an impairment of the measurement. Generally, you should perform a basic setup again following a reset. A reset is only necessary: •...
  • Page 39: Displaying And Acknowledging Error Messages

    FieldCare FieldCare is Endress+Hauser's plant asset management tool based on FDT technology. With FieldCare, you can configure all Endress+Hauser devices and third-party devices that support the FDT standard. It is compatible with the following operating systems: WinNT4.0, Win2000 and WinXP.
  • Page 40 5.4.2 ToF Tool operating program The ToF Tool is a graphical operating software for devices from Endress+Hauser that work on the time-of-flight principle. It is used to support commissioning, data backup, signal analysis and device documentation. It is compatible with the following operating systems: WinNT4.0, Win2000 and WinXP.
  • Page 41: Hart Communication

    Levelflex M FMP43 with HART/4...20 mA Operation HART communication Apart from via local operation, you can also configure the measuring device and query measured values by means of the HART protocol. There are two options available for operation: • Operation via the universal handheld terminal, the HART Communicator DXR375. •...
  • Page 42: Commissioning

    Commissioning Levelflex M FMP43 with HART/4...20 mA Commissioning Function check Make sure that all final checks have been completed before you start up your measuring point: • “Post-installation check” checklist (→ ä 22). • “Post-connection check” checklist (→ ä 31). Switching on the measuring device When the device is switched on for the first time, the following messages appear on the display: ⇒...
  • Page 43: Basic Setup

    Levelflex M FMP43 with HART/4...20 mA Commissioning Basic setup tank shape Standard lower edge of the process connection reference point of measurement measuring cond. Unknown measuring cond. Standard empty calibr. full calibr. mapping E = empty calibr. (= zero) LN = probe length setting in 005 setting in 033 safety settings...
  • Page 44 Commissioning Levelflex M FMP43 with HART/4...20 mA The Levelflex is precalibrated at the factory to the probe length ordered so that in most cases only the application parameters, which automatically adapt the device to the measuring conditions, need to be entered. For models with a current output, the factory calibration for zero point and span F is 4 mA and 20 mA, for digital outputs and the display module 0 % and 100 %.
  • Page 45: Basic Setup With Display Vu331

    Levelflex M FMP43 with HART/4...20 mA Commissioning Basic setup with display VU331 Function "measured value" (000) ⇒ ENDRESS + HAUSER – This function displays the current measured value in the selected unit (see "customer unit" (042)) function). The number of digits after the decimal point can be selected in the "no.of decimals"...
  • Page 46 Commissioning Levelflex M FMP43 with HART/4...20 mA Bypass / pipe The "bypass / pipe" option is designed especially for the installation of probes in a bypass or a stilling well. If this option is selected, the upper blocking distance is preset to 100 mm. Coax probe (not relevant for FMP43) Select the "coax probe"...
  • Page 47 Levelflex M FMP43 with HART/4...20 mA Commissioning Function "process propert." (004) ⇒ ENDRESS + HAUSER – Use this function to adapt the device reaction to the filling speed in the tank. The setting impacts on an intelligent filter. Options: • Standard •...
  • Page 48 Commissioning Levelflex M FMP43 with HART/4...20 mA Function "probe" (032) ⇒ ENDRESS + HAUSER – Use this function to select whether the probe is uncovered or covered at the time of probe length adjustment. If the probe is uncovered, the Levelflex can determine the probe length automatically "determine length"...
  • Page 49 Levelflex M FMP43 with HART/4...20 mA Commissioning E = empty calibration (= zero) E max = probe length – lower blocking distance L00-FMP4xxxx-14-00-06-en-008 Function "full calibr." (006) ⇒ ENDRESS + HAUSER – This function is used to enter the distance from the minimum level to the maximum level (=span). 100% F = full calibration (= span) F max = E –...
  • Page 50 Commissioning Levelflex M FMP43 with HART/4...20 mA Display (008) ⇒ ENDRESS + HAUSER – The distance measured from the reference point to the product surface and the meas. value calculated with the aid of empty calibration are displayed. Check whether the values correspond to the actual measured value or the actual distance.
  • Page 51 Levelflex M FMP43 with HART/4...20 mA Commissioning Note! If the probe is free, the mapping should be confirmed with "probe free". Dist. too small • At the moment, an interference echo is being evaluated • Therefore, a mapping is carried out including the echoes currently measured •...
  • Page 52 Commissioning Levelflex M FMP43 with HART/4...20 mA The distance measured from the reference point to the product surface and the measured value calculated with the aid of the empty calibration are displayed again. Check whether the values correspond to the actual meas. value or the actual distance. The following cases can occur: •...
  • Page 53: Blocking Distance

    Levelflex M FMP43 with HART/4...20 mA Commissioning Blocking distance Function "upper block. dist" (059) ⇒ ENDRESS + HAUSER – For rod probes and for rope probes with lengths of up to 8 m, the upper blocking distance is set to 0.2 m at the factory.
  • Page 54 Commissioning Levelflex M FMP43 with HART/4...20 mA Maximum measured error Typical values under reference operating conditions: DIN EN 61298-2, percentage values with reference to the span. Output: Digital Analog Sum of non-linearity, ±3 mm ± 0.06 % non-repeatability and hysteresis Offset / zero point ±4 mm ±...
  • Page 55: Envelope Curve With Vu331

    Levelflex M FMP43 with HART/4...20 mA Commissioning Envelope curve with VU331 After the basic setup, it is recommended to evaluate the measurement with the aid of the envelope curve ("envelope curve" (0E)) function group) 6.6.1 Function "plot settings" (0E1) ⇒ ENDRESS + HAUSER –...
  • Page 56: Function "Envelope Curve Display" (0E3)

    Commissioning Levelflex M FMP43 with HART/4...20 mA Function "envelope curve display" (0E3) You can obtain the following information from the envelope curve display in this function: quality of evaluated echo full calibr. evaluated echo empty calibr. is marked envelope curve minimum distance maximum distance distance of...
  • Page 57 Levelflex M FMP43 with HART/4...20 mA Commissioning Horizontal zoom mode Press , to switch to the envelope curve navigation. You are now in the horizontal zoom mode. Either is displayed. You now have the following options: • increases the horizontal scale. •...
  • Page 58: Basic Setup With The Tof Tool

    Commissioning Levelflex M FMP43 with HART/4...20 mA Exiting the navigation • Press again to run through the different modes of the envelope curve navigation. • Press to exit the navigation. The set increases and shifts are retained. Only when you reactivate the "recording curve"(0E2) function does the Levelflex use the standard display again.
  • Page 59 Levelflex M FMP43 with HART/4...20 mA Commissioning Basic setup step 2/6: • Enter the application parameters: – tank properties (for a description, → ä 45) – medium properties (for a description, → ä 46) – process properties (for a description, → ä 47) l00-fmp4xxxx-20-00-00-en-002 Basic setup step 3/6: •...
  • Page 60 Commissioning Levelflex M FMP43 with HART/4...20 mA Basic setup step 4/6: • Enter the application parameters: – probe length (for a description, → ä 47) – probe (for a description, → ä 48) – probe length (for a description, → ä 48) –...
  • Page 61 Levelflex M FMP43 with HART/4...20 mA Commissioning Basic setup step 6/6: • Interference echo suppression takes place in this step • The measured distance and the current measured value are always displayed in the header • For a description, → ä 51) l00-fmp4xxxx-20-00-00-en-006.gif Endress + Hauser...
  • Page 62 Commissioning Levelflex M FMP43 with HART/4...20 mA 6.8.1 Envelope curve with the ToF Tool After the basic setup, it is recommended to evaluate the measurement with the aid of the envelope curve (→ ä 62). L00-FMP4xxxx-20-00-00-en-007 Note! In the event of severe interference echoes, installing the Levelflex at another point can optimize the measurement routine.
  • Page 63 Levelflex M FMP43 with HART/4...20 mA Commissioning Evaluating the measurement: • The map must correspond to the course of the envelope curve (for rod probes up to approx. 5 cm and for rope probes up to approx. 25 cm before the end of the probe) when the tank is empty. •...
  • Page 64: Maintenance

    They contain the related replacement instructions. All the spare parts kits which you can order from Endress+Hauser for repairs to the Levelflex M are listed with their order numbers on → ä 73 and 75. Please contact Endress+Hauser Service for further information on service and spare parts.
  • Page 65: Accessories

    Levelflex M FMP43 with HART/4...20 mA Accessories Accessories Weather protection cover A weather protection cover made of stainless steel is recommended for outdoor mounting (order No: 543199-0001). The shipment includes the protective cover and tension clamp. F12 / F23 / T12 housing M IC M IC O rd...
  • Page 66: Remote Display And Operation, Fhx40

    Accessories Levelflex M FMP43 with HART/4...20 mA Remote display and operation, FHX40 Wall-mounting Pipe-mounting (without mounting bracket) (mounting bracket and plate supplied optionally, s. product structure) Separate housing FHX 40 (IP 65) Micropilot M Levelflex M Prosonic M O rd O rd r.
  • Page 67: Commubox Fxa191 Hart

    TI404F/00/en. Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field devices with CDI interface (= Endress+Hauser Common Data Interface) to the USB port of a computer or laptop. For details refer to TI405C/07/en. Note! For the following Endress+Hauser devices you need the "ToF Adapter FXA291" as an additional accessory: •...
  • Page 68: Troubleshooting

    Connect the plug Ready Display works? of the display. correctly Output current between The display is possibly defective. 3.6 …22mA ? Contact Endress+Hauser Service Not ok Output current Correct the Check cabling Current is ok? Ready < 3.6 mA ? (2 wire) cabling <...
  • Page 69: System Error Messages

    Levelflex M FMP43 with HART/4...20 mA Troubleshooting System error messages Code Description Possible cause Remedy A102 checksum error device was switched off before data were reset total reset & new calibr. stored; avoid EMC problems; required. EMC problem; if alarm prevails after reset, PROM defective exchange electronics W103...
  • Page 70 Troubleshooting Levelflex M FMP43 with HART/4...20 mA Code Description Possible cause Remedy A261 HF cable defective HF cable defective or HF connector loose check HF connector, replace cable if defective W275 offset too high temperature at the electronics too high or check temperature, replace HF HF module defective module if defective...
  • Page 71: Application Errors

    Levelflex M FMP43 with HART/4...20 mA Troubleshooting Application errors Error Output Possible cause Remedy A warning or alarm Depending on the configuration See table of 1. See table of error messages (→ ä 69) has occurred. error messages (→ ä 69) →...
  • Page 72 Troubleshooting Levelflex M FMP43 with HART/4...20 mA Device displays a Incorrect probe length 1. Carry out automatic probe length level when the detection when the tank is tank is empty. empty. 20 mA/100% 2. Carry out mapping over entire probe when the tank is empty (probe free!).
  • Page 73: Spare Parts

    Spare parts Note! You can order spare parts directly from your Endress+Hauser Service organization by giving the serial number which is printed on the transmitter nameplate (→ ä 8). The corresponding spare part number also appears on each spare part. Installation instructions are given on the instruction card that is also supplied.
  • Page 74 Troubleshooting Levelflex M FMP43 with HART/4...20 mA 10 Housing Only for E+H service. 11 Hood for terminal compartment 52006026 Cover for the connection compartment F12 52019062 Cover for the connection compartment F12, FHX40 12 Set of screws 535720-9020 Set of screws for housing F12/T12 20 Cover 52005936 Cover F12/T12 aluminium, inspection glass, seal 517391-0011 Cover F12/T12 aluminium, coated, seal...
  • Page 75 Levelflex M FMP43 with HART/4...20 mA Troubleshooting 9.4.3 Spare parts Levelflex M FMP43 with housing T12 L e v O rd e lf le d e : r. -N o .: s s b e re a s u ic h r in g ra n 6 ..
  • Page 76 Troubleshooting Levelflex M FMP43 with HART/4...20 mA 10 Housing Only for E+H service. 11 Hood for terminal compartment 52005643 Hood T12 12 Set of screws 535720-9020 Set of screws for housing F12/T12 20 Cover 52005936 Cover F12/T12 aluminium, inspection glass, seal 517391-0011 Cover F12/T12 aluminium, coated, seal 25 Cover for the connection compartment 518710-0020 Cover T3/T12, aluminium, coated, seal...
  • Page 77 Levelflex M FMP43 with HART/4...20 mA Troubleshooting 9.4.4 Spare parts Levelflex M FMP43 - probes, accessories and spare parts M IC O rd C od S er P IL o. : M IC M es O rd sb er M ea C od su rin ei ch...
  • Page 78 Troubleshooting Levelflex M FMP43 with HART/4...20 mA 50 Sensor body 71043416 Sensor body FMP43, compact 71043418 Sensor body FMP43, compact, detachable 71043420 Sensor body FMP43, detachable, cable 3m 71043421 Sensor body FMP43, detachable, cable 6m 52 Process connection 71043422 Flange 1-1/2" 150lbs RF, 316L 71043424 Flange 2"...
  • Page 79 Levelflex M FMP43 with HART/4...20 mA Troubleshooting 55 Probe without process connection Probe: 300mm-4000mm/12in-157in K ..mm, Stab 8mm, 316L, Ra<0.8um/150grit M ..in, Stab 8mm, 316L, Ra<0.8um/150grit ..mm, Stab 8mm, 316L, electro polished Ra<0.38um/240grit ..in, Stab 8mm, 316L, electro polished Ra<0.38um/240grit O-ring Material;...
  • Page 80: Return

    Documentation 07.2007 V 01.04.02 Original software. BA357F/00/en/07.07 71040911 BA245F/00/en/07.07 71040937 Contact addresses of Endress+Hauser Contact addresses can be found on our homepage: www.endress.com/worldwide. If you have any questions, please do not hesitate to contact your Endress+Hauser representative. Endress + Hauser...
  • Page 81: Technical Data

    Levelflex M FMP43 with HART/4...20 mA Technical data Technical data 10.1 Additional technical data 10.1.1 Input The measured variable is the distance between the reference point (see Fig on → ä 14) and the Measured variable product surface. The level is calculated subject to the empty distance entered (E, see Fig. on → ä 90). Alternatively, the level can be converted by means of linearization (32 points) to other variables (volume, mass).
  • Page 82 Technical data Levelflex M FMP43 with HART/4...20 mA Influence of ambient The measurements are carried out in accordance with EN 61298-3: temperature • Digital output (HART, PROFIBUS PA, FOUNDATION Fieldbus): – average T : 0.6 mm/10 K, max. ±3.5 mm over the entire temperature range -40 °C to +80 °C 2-wire: •...
  • Page 83 Levelflex M FMP43 with HART/4...20 mA Technical data Degree of protection • With closed housing tested according to – Housing F12/T12: IP68, NEMA6P (24 h at 1.83 m under water) – Housing F23: IP69K in combination with cable entries M20 G ½ and NPT ½ –...
  • Page 84 Technical data Levelflex M FMP43 with HART/4...20 mA 10.1.6 Mechanical construction Tolerance of probe length Tolerance Rod length + 0 / - 3 mm < 1000 mm + 0 / - 5 mm 1000 to < 4000 mm Weight Part Weight T12 housing approx.
  • Page 85 10.1.7 Certificates and approvals CE approval The measuring system meets the legal requirements of the EC guidelines. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. Certificates Correlation of safety instructions (XA) to the instrument:...
  • Page 86 The gap-free connections can be cleaned without residue using the usual cleaning methods. Many versions of Levelflex M meet the requirements of the 3A-Sanitary Standard No. 74. Endress+Hauser confirms this compliance by affixing the 3A symbol. Overfill protection SIL 2, for 4 to 20 mA output signal (see SD174F/00/en "Functional Safety Manual").
  • Page 87 Levelflex M FMP43 with HART/4...20 mA Technical data Endress + Hauser...
  • Page 88: Appendix

    Appendix Levelflex M FMP43 with HART/4...20 mA Appendix 11.1 HART operating menu (display module), ToF Tool basic setup tank properties medium cond. process proper. end of probe 030 determine length empty calibr. enter value standard unknown standard see Function group “leghth adjustment 03” aluminium tank DC: 1.4 …...
  • Page 89 Levelflex M FMP43 with HART/4...20 mA Appendix full calibr. dist./meas.value check distance range of mapping start mapping dist./meas.value enter value distance = ok input of D and L dist. too small mapping range are displayed D and L manual are displayed probe free dist.
  • Page 90: Description Of Functions

    Appendix Levelflex M FMP43 with HART/4...20 mA 11.2 Description of functions Note! A detailed description of the function groups, functions and parameters is given in the documentation BA245F – "Description of Device Functions" on the CD-ROM supplied. 11.3 Function and system design 11.3.1 Measuring principle) The Levelflex is a "downward-looking"...
  • Page 91 • With a personal computer, FXA193 (RS232C) or FXA291 and ToF Adapter FXA291 (USB) and the operating software "ToF Tool - FieldTool Package" or "FieldCare". The ToF Tool is a graphical operating software for devices from Endress+Hauser (radar, ultrasonic, guided micro-pulse). It assists with commissioning, data backup, signal analysis and documentation of the measuring point.
  • Page 92 Appendix Levelflex M FMP43 with HART/4...20 mA Endress + Hauser...
  • Page 93: Index

    Levelflex M FMP43 with HART/4...20 mA Index Index Menu structure ....... . . 88 Alarm .
  • Page 94 Levelflex M FMP43 with HART/4...20 mA Index Endress + Hauser...
  • Page 95 Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
  • Page 96 www.endress.com/worldwide BA357F/00/en/07.07 No. 71040912 CCS/FM+SGML 6.0/ProMoDo 71040912...

Table of Contents