Emc And Environmental Type Tests - Siemens RUGGEDCOM RX1510 Installation Manual

Rugged multi service platforms
Hide thumbs Also See for RUGGEDCOM RX1510:
Table of Contents

Advertisement

6.2

EMC and Environmental Type Tests

The RUGGEDCOM RX1510 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Test for IEC 61850-3
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-29
IEC 60255-5
RUGGEDCOM RX1510
Installation Manual, 10/2021, C79000-G8976-1055-21
Test
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced
(Conducted) RFI
Magnetic Field
Voltage Dips
and Interrupts
Damped Oscillatory
Mains Frequency
Voltage
Ripple on DC
Power Supply
Voltage Dips
and Interrupts
Dielectric Strength
6.2 EMC and Environmental Type Tests
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Enclosure Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
DC Power Ports
DC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Certification
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
10 V
100 A/m, continuous
1000 A/m for 1 s
1000 A/m for 1 s
30% for 1 period
60% for 50 periods
2.5 kV common, 1 kV
differential mode @1 MHz
30 V Continuous
300 V for 1 s
10%
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (Failsafe Relay output)
1.5 kV
2 kV
Severity
Levels
4
a
Note
4
4
3
4
3
a
Note
5
 
3
4
3
 
 
39