Table of Contents

Advertisement

Available languages

Available languages

7.9

Lockout types

Whenever a lockout occurs, the control box shows the reasons
for the fault (and the reasons can be identified by the reset button
colour). The sequence of pulses issued by the control box of the
Lockout description
Presence of extraneous light
when the motor starts
Pre-heating not terminated (*)
Presence of extraneous light
detected during pre-purging
The flame is not detected after
the safety time
Flame failure during operation
Fan motor error
Fault in the 1st stage oil valve's
electronic control circuit
Fault in the 2nd stage valve's
electronic control circuit
Eeprom error
(*) only for suitable applications
Blink frequency of the reset button for status indication (see par-
agraph "Fault diagnostics - lockouts" on page 28).
To reset the control box after visual diagnostics
have been displayed, you must press the reset
button.
WARNING
In the event the burner stops, in order to prevent any
damage to the installation, do not unblock the burner
more than twice in a row. If the burner locks out for a
third time, contact the customer service.
WARNING
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
DANGER
manual and in compliance with the standards and
regulations of current laws.
Start-up, calibration and operation of the burner
Lockout time
After 25 seconds
After 600 seconds
2.5 sec OFF
After 25 seconds
After 5 seconds
after the activation of
the oil valve
After 3 recycles
Immediate
Immediate
Immediate
Immediate
LED in the reset button identifies the possible types of fault, which
are listed in the table below:
Led colour
-
presence of a false flame signal after heat request.
-
fault with the resistor of the oil pre-heater (*)
-
fault with the switch or start up thermostat (*)
0.5 sec ON
-
the bridge socket P is not connected, or the heater is
faulty
-
presence of false flame signal during pre-purging
RED
-
flame sensor defective or dirty
Steady ON
-
oil valve defective or dirty
-
faulty ignition transformer
-
badly regulated burner
-
no fuel oil
-
burner not calibrated correctly
-
oil valve defective or dirty
-
flame sensor defective or dirty
-
faulty fan motor
-
fan motor not connected
-
faulty oil valve
-
fault inside the electronic circuit controlling the oil
valve
-
internal control circuit of the 2nd stage gas valve faulty
-
faulty internal memory
35
GB
Probable cause
Tab. Q
20135920

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents