6.1.9 Other Approvals; Emc And Environmental Type Tests - Siemens SIMATIC NET RUGGEDCOM RX5000 Installation Manual

Hide thumbs Also See for SIMATIC NET RUGGEDCOM RX5000:
Table of Contents

Advertisement

Certification
6.1.9 Other Approvals
6.1.9
Other Approvals
This device meets the requirements of the following additional standards:
6.2

EMC and Environmental Type Tests

The RUGGEDCOM RX5000 has passed the following EMC and environmental tests.
IEC 61850-3 EMC Type Tests
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
40
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
IEC 61850-3
Communications Networks and Systems for Power Utility Automation – Part 3:
General Requirements
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
Test
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced
(Conducted) RFI
Magnetic Field
Voltage Dips
& Interrupts
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Signal ports
D.C Power ports
AC Power ports
Earth ground ports
Enclosure Ports
DC Power ports
Test Levels
+/- 8 kV
+/- 15 kV
20 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV
+/- 4 kV
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
+/- 2 kV line-to-earth,
+/- 1 kV line-to-line
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
10 V
10V
10V
10V
100 A/m
1000 A/m for 1 s
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
RUGGEDCOM RX5000
Installation Manual, 01/2021, C79000-G8976-1058-13
Severity
Levels
4
4
a
Note
a
Note
4
4
4
4
3
4
3
3
3
3
 
5
 