TECHNICAL DATA SPECIFICATIONS
Fuel
Firing rate
Effective output
Voltage (single phase)
Absorbed electrical power
Motor (rated)
Capacitor
Pump pressure
Primary control
Ignition transformer
BURNER AND MOUNTING FLANGE DIMENSIONS
Model F15
A
Inches
11 3/4
13 25/32
mm
298
E1: 10-inch long (254mm) tubes are also available.
BURNER COMPONENTS IDENTIFICATION
1
2
3
4
20101932
5
BURNER COMPONENTS
1 Lockout indicator lamp and Reset
button
2 Primary control
3 Primary control sub-base
4 Pump pressure regulator adjustment
screw
5 Motor
6 Capacitor
7 Air adjustment fixing screws
8 Air shutter
9 End cone
2902555
No. 2 Fuel Oil
2.55 to 5.75 GPH
8.2 to 18.6 kg/h
357,000 to 805,000 BTU/h - 104.6 to 235.8 kW
89,960 to 202,860 kcal/h
120V 60Hz (+ 10% - 15%)
450 Watts
3250 rpm Run Current 4 AMP
16 Microfarads 260V
100 to 200 psi
RIELLO 530 SE/C
8kV 16mA
B
C
D
9 1/16
4 11/16
350
230
119
6
8
7
10 Turbulator adjustment screw
11 Air tube cover
12 Coil
13 Vacuum gauge connection port
14 Pressure gauge and bleeder port
15 Return fuel line port
16 Supply fuel line port
17 Adjustable collar
18 Mounting flange with gasket
19 24V thermostat connections
20 Solenoid valve
E
F
5
11 27/32
127
301
9
17
10
18
19
16
15
2
D8860
G
H
I
1 1/2
1/4
7/16
38
6
11
11
12
13
14
G
6 17 / 32 " - 166 mm
8 1 / 4 " - 210 mm
9 1 / 4 " - 235 mm
GB
B
E
F
E1
L
2 7/8
73
D6000