Installing the Device
2.6.1 Connecting AC or DC Power
2.6.1
Connecting AC or DC Power
To connect a single high AC, high DC or low DC power supply to the device, do the
following:
Electrical hazard – risk of damage to equipment
Before testing the dielectric strength (HIPOT) in the field, remove the metal jumper.
This metal jumper connects transient suppression circuitry to chassis ground and
must be removed in order to avoid damage to transient suppression circuitry during
testing.
Electrical hazard – risk of damage to equipment
Do not connect AC power cables to a DC power supply terminal block. Damage to
the power supply may occur.
1.
2.
3.
16
Equipment must be installed according to applicable local wiring codes and stan-
dards.
CAUTION
CAUTION
Remove the terminal block cover.
Identify the internal power module (POWER 1 or POWER 2) appropriate for the
power supply (AC or DC).
Use these screws along with #6 ring lugs to secure the wires to the terminal
block.
Note
For wiring options, refer to
"Wiring Examples (Page
18)".
RUGGEDCOM RSG2100F
Installation Manual, 01/2020, C79000-G8976-1344-07