Gemü Conexo; Correct Use - GEM 0324 Operating Instructions Manual

Electrically operated pilot solenoid valve
Table of Contents

Advertisement

4 GEMÜ CONEXO
4 GEMÜ CONEXO
In the corresponding design with CONEXO, this product has
an RFID chip for electronic identification purposes. The posi-
tion of the RFID chip can be seen below. The CONEXO pen
helps read out information stored in the RFID chips. The CON-
EXO app or CONEXO portal is required to view this informa-
tion.
Installing the RFID chip
RFID chip

5 Correct use

Danger of explosion
▶ Danger of death or severe injury.
Only use the product in potentially ex-
plosive zones confirmed in the declara-
tion of conformity.
Improper use of the product
▶ Risk of severe injury or death.
▶ Manufacturer liability and guarantee will be void.
Only use the product in accordance with the operating
conditions specified in the contract documentation and in
this document.
1. Use the product in accordance with the technical data.
The GEMÜ 0324 directly controlled 3/2-way pilot solenoid
valve is designed for direct mounting to pneumatically oper-
ated valves. The body is made of plastic. The coil is plastic
encapsulated.
GEMÜ 0324
DANGER
WARNING
5.1 Product without ATEX, code 06, 08, 09
The product is not intended for use in potentially explosive
areas.
5.2 Product with ATEX, code 04, 05, 07, 11
The product with the ATEX ordering option is intended for use
in potentially explosive areas of zone 2 with gases, mists or
vapours and zone 22 with combustible dusts in accordance
with EU directive 2014/34/EU (ATEX).
The product has the following explosion protection marking:
Gas:
II 2G Ex mb II T4
Dust:
II 2D Ex tD A21 IP65 T130°C
Type examination certificate: PTB 03 ATEX 2018 X
The product has been developed in compliance with the fol-
lowing harmonised standards:
DIN EN 60079-0:2012+A11:2013
DIN EN 60079-7:2015
DIN EN 60079-15:2010
DIN EN 60079-31:2014
Use of the product is permissible in the following ambient
temperature ranges: 0 to +60 °C
For use in potentially explosive areas, the following
conditions or operation limits must be observed:
The following special conditions must be complied with:
1. Connection cables and connectors must be protected
from damage.
2. Layers of dust > 5 mm must be removed.
3. Warning label "Danger from electrostatic build-up".
4. Warning label "Do not disconnect when live".