Viessmann Vitodens 200-W WB2B 80 Start-Up/Service Instructions page 33

Wall-mounted, natural gas-fired condensing boiler
Hide thumbs Also See for Vitodens 200-W WB2B 80:

Advertisement

Outdoor Reset Programming Unit
Connecting the boiler control to a LON system
(continued)
Vitocom LON Communication Module (accessory) must be connected.
Installation Instructions
LON Communication Module
Note:
Data transfer via LON can take several minutes.
Single-boiler system with Vitotronic 200-H, HK1M and Vitotronic 200-H, HK1S
mixing valve controls and Vitocom LON communication module
Set up the LON participant numbers and other functions via coding level 2
(see table below).
Note:
In the same LON system, a number cannot be allocated twice.
Only one Vitotronic may be programmed as fault manager.
Boiler Control
Vitotronic 200-H
Unit
(e.g. HK1M mixing
valve control)
LON
Participant no. 1
Participant no. 10
Code "77:1"
Code "77:10"
Control unit is
Control unit is not
fault manager
fault manager
Code "79:1"
Code "79:0"
Control unit
Control unit
transmits the
receives the time
time
Set code "81:3"
Code "7b:1"
Control unit
Control unit
receives outdoor
transmits outdoor
temperature
temperature
Set code "97:2"
Set code "97:1"
LON participant
LON participant
fault monitoring
fault monitoring
Code "9C:20"
Code "9C:20"
*1
Refer to separate Installation Instructions of accessories.
Control Technology
Vitotronic 200-H
*1
(e.g. HK1S
multiple mixing
valve control)
LON
LON
Participant no. 11
Code "77:11"
Control unit is not
fault manager
Code "79:0"
Control unit
receives the time
Set code "81:3"
Control unit
receives outdoor
temperature
Set code "97:1"
LON participant
fault monitoring
Code "9C:20"
*1
Vitocom
LON
communication
module
Participant no. 99
Device is fault
manager
Device receives
the time
--
--
33