Initial Start-up and Service
Steps
(continued)
I
nitial start-up
I
nitial start-up
Uhrzeit
Datum
0 0 0 0 4 4 4 4 . . . . 0 0 0 0 8 8 8 8 . . . . 0 0 0 0 7 7 7 7
Sa
12
4. Check power supply connection
A power/pump module is supplied with
the Vitodens 200-W, WB2B boiler,
which requires a 120VAC power
supply from a wall receptacle.
The module contains a 120/230VAC
step-up transformer to power the boiler
with 230VAC. Refer to the Installation
Instructions shipped with the module
for wiring details and/or the Installation
Instructions of the boiler.
Voltage range
The voltage at connector fÖ of the
boiler control must be 230V (see wiring
diagram).
Neutral conductor
The electrical power supply must have
a neutral conductor.
5. Set time and date
See page 26 in these instructions for an overview of controls and indicators of
the boiler control.
H During commissioning or after a
prolonged time not in use, it may be
necessary to reset the time and date
if the time flashes in the display.
H When the boiler is started up for the
first time the display appears in
German (factory default setting).
Refer to following subsection on how
to select the correct language.
1. Press "⊕ /
" to adjust to the
current time.
2. Press "
" to confirm. The word
"Datum" is displayed.
3. Press "⊕ /
" to set the current
date.
4. Press "
" to confirm.
IMPORTANT
In Canada all electrical wiring is to be
done in accordance with the latest
edition of CSA C22.1 Part 1 and/or
local codes. In the U.S. use the
National Electrical Code ANSI/NFPA
70. The heating contractor must also
comply with both the Standard for
Controls and Safety Devices for
Automatically Fired Boilers, ANSI,
ASME CSD-1.
Please note:
The outer conductor "L" and the
neutral conductor "N" must not be
interchanged.
See wiring diagram on page 68 in
section entitled "Additional
Information".
Please note:
If any fault exists during the initial
start-up "storung" (fault) appears
on the screen. Read and record
the fault. Press " i " and read
the fault. "Quittieren? Ja"
(acknowledge? Yes). Press "
then proceed with setting the time
and date.
"