7. FUNCTIONS

7-1. Explanation of Functions

The numerical values such as temperature, frequency, time and current in parentheses are an example
NOTE
of SAP-CMRV3146EH and the values are different from the other models.
Control/conditions
INITIAL
Breaker is ON.
The ON/OFF operation
button on the remote
controller is pressed.
HEAT
The ON/OFF operation
button on the remote
controller is pressed.
The room temperature
has reached the desired
temperature.
The thermostat turns
OFF.
The indoor and outdoor
temperatures are high.
The thermostat turns ON.
Unit operation
If automatic operation mode has been selected
with the remote controller, operation begins in
HEAT, SENSOR DRY, or COOL mode
depending on the room temperature and
outdoor temperature at the time operation starts.
Depending on the operational mode, refer to the HEAT, SENSOR DRY, or COOL item.
Operation lamp illuminates.
Indoor fan is stopped to prevent cold air from
being emitted.
Outdoor unit begins operating after
forced-stop is canceled.
When the indoor coil temperature rises,
the compressor starts,
the outdoor fan starts,
and the indoor fan changes from "LL"
to the set fan speed.
When the frequency reaches
increases are stopped for a period of
(Refor to Table 2 "Freguency control".)
The frequency then increases.
The indoor temperature and the remote
controller temperature setting are
approximately equal.
The indoor fan is stopped.
In order to protect the compressor, the outdoor
unit will not operate for 3 minutes after the
thermostat turns OFF, even if the room
temperature drops below the desired
temperature.
The frequency is not increased, even if
there is a difference between the room
temperature and the desired temperature.
In some cases, the frequency may be
decreased.
The indoor unit is stopped.
Power is supplied to the indoor and outdoor unit
control circuits, however the unit remains stopped.
Positioning of the outdoor unit electric expansion
valve is performed.
This applies in the case of automatic
HEAT/COOL operation.
The unit is forced to stop for 3 minutes after
the power is turned ON, or 3 minutes after the
compressor stops, in order to protect the
compressor.
The frequency is increased at the rate of 1 Hz
every 0.5 seconds.
Depending on the relationship between the
remote controller temperature setting and the
room temperature, the compressor may stop
temporarily (in other words, the thermostat
may turn OFF).
Hz,frequency
This is in order to stabilize the return of oil to the
seconds.
compressor.
If the indoor and outdoor temperatures are high,
the current peak cut-off activates, stopping any
increases in frequency.
Operating frequency is stabilized in order to
maintain a comfortable environment.
The outdoor unit stops. (It does not stop if the
thermostat for another indoor unit is ON.)
Approximately 30 seconds after the
thermostat turns OFF, the indoor fan is
stopped.
The outdoor unit starts automatically after 3
minutes.
During these 3 minutes, a low-pressure
pressure balance is achieved, allowing the
compressor to start more easily.
The amount of heat pump exceeds the amount
of heat radiation from the room.
Therefore, there is no need to further increase
the compressor capacity, and the frequency is
stabilized or lowered.
The unit operated before, and the temperature of
the indoor heat exchanger is relatively warm.
Therefore,the fan speed may start at the set fan
speed at the same time that the thermostat turns
ON.
64
Explanation