3. FRONT PANEL CONTROLS & BASIC OPERATION
3.2

Basic Operation

Refer to section 5 for a full description of each parameter.
3.2.1

General

(1) The inverter does not have a main power switch and is live when the mains supply is connected. It waits,
with the output disabled, until the RUN button is pressed or for the presence of a digital ON signal at
terminal 5 (rotate right) or terminal 6 (rotate left) - see parameters P051 - P053.
(2) If output frequency is selected to be displayed (P001 = 0), the corresponding setpoint is displayed
approximately every 1.5 seconds while the inverter is stopped.
(3) The inverter is programmed at the factory for standard applications on Siemens four-pole standard motors.
When using other motors it is necessary to enter the specifications from the motor's rating plate into
parameters P081 to P085 (see Figure 3.2.1). Note: Access to these parameters is not possible unless
P009 has been set to 002 or 003.
Figure 3.2.1: Typical Motor Rating Plate Example
Note:
Ensure that the inverter is configured correctly to the motor, i.e. in the above example delta terminal
connection is for 220 V.
3.2.2

Initial Testing

(1) Check that all cables have been connected correctly (section 2) and that all relevant product and
plant/location safety precautions have been complied with.
(2) Apply mains power to the inverter.
(3) Ensure that it is safe to start the motor. Press the RUN button on the inverter. The display will change to 5.0 and
the motor shaft will begin to turn. It will take one second for the inverter to ramp up to 5 Hz.
(4) Press the STOP button. The display will change to 0.0 and the motor slow to a complete stop within one second.
© Siemens plc 1999
P081
50 Hz
cos ϕ 0,81
VDE 0530
P083 P082
P084
3 Mot
1LA5053-2AA20
IEC 56
Nr. E D510 3053
IM B3
IP54
220/380 V ∆ /Y
60 Hz
0,61/0,35 A
0,12
kW
cos ϕ 0,81
2745
/min
S.F. - 1,15
P085
19
English
12 022
Rot. KL 16
I.Cl.F
440 V Y
0,34 A
0,14 kW
3310 /min
G85139-H1750-U049-C1
19/08/99

Advertisement

Table of Contents
loading

Table of Contents