Switching Times; Circuit Diagrams - Siemens SION Operating Instructions Manual

Vacuum circuit-breaker
Hide thumbs Also See for SION:
Table of Contents

Advertisement

Closing time
Opening time
1st shunt release
2nd/3rd release
Arcing time
Break time
1st shunt release
2nd/3rd release
Dead time
Closed/open contact time
1st shunt release
2nd/3rd release
Minimum command duration
Closing solenoid
1st shunt release
2nd/3rd release
Shortest pulse time for circuit-breaker tripping signal (-S6)
1st shunt release
2nd/3rd release
Charging time if actuated electrically
Synchronous error between the poles
9229 0025 176 0E
2021-11-15

Switching times

Fig. 45
Switching times
Closing time = period between starting (command) of the closing movement and
the moment of contact with all poles.
Opening time = period between starting (command) of the opening movement and
opening of the last pole.
Arcing time = period from the start of the first arc to extinction of the arcs in all poles.
Break time = period between starting (command) of the opening movement and ex-
tinction of the arc in the pole extinct last (= opening time + arcing time).
Closed-open contact time = period in a CLOSED-OPEN operating cycle between
the moment of contact in the first pole during closing and the time when contact has
been broken in all poles during subsequent opening.
Dead time = period from the end of the current flow in all poles up to the start of the
current flow in the first pole.

Circuit diagrams

The circuit diagrams for the vacuum circuit-breaker are compiled depending on your
order.
The corresponding circuit diagram book can also be downloaded from the following
URL on the internet: https://support.industry.siemens.com
(-Y1)
(-Y2 to -Y7)
(-Y1)
(-Y2 to -Y7)
(-Y1)
(-Y2 to -Y7)
(-Y9)
(-Y1)
(-Y2 to -Y7)
(-Y1)
(-Y2 to -Y7)
(-M1)
Description
≤ 60 ms
≤ 30 ms
≤ 45 ms
< 15 ms
≤ 45 ms
≤ 60 ms
300 ms
≤ 45 ms
≤ 60 ms
45 ms
40 ms
20 ms
> 10 ms
> 6 ms
< 15 s
≤ 2 ms
37