Using Reydisp Manager 2

5.3 Transmitting the Configuration to a 7SR5 Device for the First Time

5.3
Transmitting the Configuration to a 7SR5 Device for the First Time
When the device is delivered from the factory it will display a message intermittently on the fascia advising the
device is not configured. Changing any parameter setting from the fascia or sending a device configuration
file will remove this message. The similar message advising that the IEC 61850 is not configured, will be
removed if a configuration is sent to the device. This message can be disabled by setting of the user setting
IEC 61850 Configuration Alert if this protocol is not to be used. Before commissioning a device, as a
minimum, the device must be paramerterized from the fascia. It is recommended that the device is fully
configured from the Reydisp Manager 2 PC software.
In Reydisp Manager 2, initialization with a configuration associates the offline configuration with the 7SR5
device. For this, the 7SR5 device transmits its serial number, which is then entered in the corresponding
offline configuration.
[sc_7SR5_SendDeviceConfiguration, 1, --_--]
Figure 5-10
In the project tree, select the device of the offline configuration and in the device tasks menu click Send
Device Configuration.
Alternatively click the Send button in the Device Details screen on the right hand side.
The Send Device Configuration window opens and the user can then select the connection method. Select
Connect by USB for first time connection to the relay.
Reydisp Manager 2 recognizes automatically that the device is connected via USB cable.
68
Send Device Configuration
Reyrolle 7SR5, Operating, Manual
C53000-B7040-C013-1, Edition 05.2021