Operation Options; General; Online Operation Using Reydisp Manager 2 - Siemens Reyrolle 7SR5 Operating Manual

Hide thumbs Also See for Reyrolle 7SR5:
Table of Contents

Advertisement

In Service Operation

7.3 Operation Options

7.3
Operation Options

General

7.3.1
The device is operated via a Reydisp Manager 2 PC or directly using the fascia keys. You have the following
operating options during operation:
Readout of indications
Readout, backup, and deletion of logs and records
Resetting event counters
Changing device settings such as date, time, and interface language
Changing passwords/Confirmation ID
Changing function parameters and switching of settings groups
Controlling equipment
i
i
NOTE
Reydisp Manager 2 Communication
Operation using a Reydisp Manager 2 PC requires a functioning communication connection from the
Reydisp Manager 2 PC to the device. For this purpose, you can use the USB interface on the fascia, the inte-
grated or other Ethernet interfaces.
i
i
NOTE
Protection from Operating Errors and Unauthorized Access
Operator
Changes to device settings and the deletion of process data can be prevented by enabling the setting
confirmation IDs. After entering the setting ID, if no action takes place within certain times (60
minutes after the last key press, or if the Control ID is entered), an open confirmation query is auto-
matically terminated. Every action carried out within these times restarts the time. After a confirma-
tion query has ended you must confirm changes in device settings again by entering confirmation IDs.
Before modified settings or the activation of control commands is accepted, there will be additional
requests to enter the confirmation ID. You acknowledge these requests directly on the on-site opera-
tion panel by pressing the front fascia buttons. You confirm the interactive dialog in Reydisp Manager
2 by mouse click.

Online Operation Using Reydisp Manager 2

7.3.2
During online operation, you establish a direct connection to the device to be operated. You use this method
for:
Commissioning
Test and diagnostics
Changing settings in the operating state
Online operation with Reydisp Manager 2 is beneficial in these operating modes, a device must be added to
the project and the configuration transferred from the connected device. As soon as you have created the
corresponding device in a project, however, only operate the device from there. Your settings are then saved
on your PC and are available for offline configuration and parameterization tasks.