Commissioning
6.5 Device Configuration
[sc_7SR5_SettingsGroupFascia, 1, --_--]
Figure 6-13

Changing Setting Group via Binary Inputs

6.5.10
For settings group switching via binary inputs on your 7SR5 device, the user must have configured the binary
input signals that are necessary for switching the settings group to the contacts of the device.
These can be found in Reydisp Manager 2 from Configuration > User Settings > Configuration > Binary
Inputs > Input Matrix.
[sc_7SR5_SettingsGroupChange, 1, --_--]
Figure 6-14

Changing Setting Groups via Communication Protocols

6.5.11
The communication protocols IEC 60870-5-103, IEC 61850, DNP3, Modbus RTU, and Modbus TCP can be used
for switching the settings groups via a communication connection. See relevant Communication and Device
manuals for detailed information.
94
Settings Group via Front Fascia
Settings Group Change via Binary Inputs
Reyrolle 7SR5, Operating, Manual
C53000-B7040-C013-1, Edition 05.2021