Figure 22 Control Board Config./Setting; Configuring Control For Erv Mod. Control - Bard I-TEC I30A1D Installation Instructions Manual

Packaged air conditioner
Table of Contents

Advertisement

ECM Motor Control Cable
To Automation
Controller
0-2,000 RPM
= 0-10Vdc
Signal Common,
Aux Common &
Neutral/Common are
internally connected
Class II Power Source
Earth neutral/Common
at transformer
for electrical safety.
CONFIGURING BARD PART #8403-067
CO
CONTROL for ERV MODULATING
2
CONTROL
BARD PART #8403-067
Carbon Dioxide and Temperature Transmitters
accurately monitorthe CO2concentration and
temperature in schools, office buildings, and otherindoor
environments to help achieve LEED® certification.
SPECIFICATIONS
Range: CO
: 0 to 2000 or 0 to 5000 ppm (depending on model)
2
Temperature: 32 to 122°F (0 to 50°C).
Accuracy: ±40 ppm + 3% of reading.
Temperature Dependence: ±8 ppm / °C at 1100 ppm.
Non-Linearity: 16 ppm.
Pressure Dependence: 0.13% of reading per mm of Hg.
Response Time: 2 minutes for 99% step change.
Ambient Operating Temperature: 32 to 122°F (0 to 50°C).
Ambient Operating Humidity: 10 to 95% RH (non-
condensing).
Power Requirements: 16 to 35 VDC / 19 to 28 VAC.
Power Consumption: Average: 2 watts; Peak: 3.75 watts.
Sensor: Single beam, dual-wave length NDIR.
Output:
Current: 4 to 20 mA (max 500 Ω );
Voltage: 0 to 5 VDC or 0 to 10 VDC (min 500 Ω );
Relay: SPST NO 2A @ 30 VDC;
RTD or thermistor per r-t curves (depending on model)
Weight: 5.6 oz (158.8 g)
Manual 2100-597
Page
40 of 52
FIGURE 22
CONTROL BOARD CONFIGURATION/SETTING
Control Signal
Signal Common
RPM Out
Common
Aux
Power
24Vac/dc
24Vac/dc
Neutral/Common
Manual adjust screw. Use when operating in manual mode ("M" jumper
installed) along with the "GREEN SIGNAL LIGHT" to adjust to the
required CFM of ventilation. CW rotation reduces the "FLOW INDEX",
CCW rotation increases the "FLOW INDEX".
Disconnect power supply before installation to prevent electrical
WARNING
shock and equipment damage.
Make sure all connections are in accordance with the job wiring diagram and in
accordance with national and local electrical codes. Use copper conductors only.
Use electrostatic discharge precautions (e.g., use of wrist straps)
CAUTION
during installation and wiring to prevent equipment damage.
Avoid locations where severe shock or vibration, excessive
CAUTION
moisture or corrosive fumes are present.
Do not exceed ratings of this device, permanent damage not
CAUTION
covered by warranty may result.
Upon powering the transmitter, the firmware version will flash on
NOTICE
the display. A warm up period of 30 minutes is required for the
transmitter to adjust to the current CO
NOTICE
Self calibration feature of the transmitter requires exposure to
normal outdoor equivalent carbon dioxide level once every thirty
days.
Move jumper pin to "P" position to
allow variable ventilation control
using 4-20MA CO2 controller
Board mode pins factory shipped
on "M" pin for On/Off control
scheme using "A" signal on low
voltage control board.
"Red" status light (on
when unit has power)
"Green" signal light continuously
indicates the flow index the blower
is producing. After a pause, the
lamp will flash out long digits which
will indicate the "TENS" count,
which is immediately followed by
short flashes between 1 and 99.
For example, a flow index of 23
would yield two long flashes and
three short flashes.
concentration.
2