Fig. 19A Erv Manual Mode "M" Terminal; Fig. 19B Erv Mod. Mode "P" Terminal - Bard I-TEC I30A1D Installation Instructions Manual

Packaged air conditioner
Table of Contents

Advertisement

ERV "MANUAL MODE" JUMPER PIN ON "M" TERMINAL
FLOW INDEX (Light
Blink Code)
ERV CFM
450
100
425
89
400
83
375
76
350
59
325
50
300
40
275
32
250
25
225
12
200
9
175
4
150
1
ERV "MODULATING MODE" JUMPER PIN ON "P" TERMINAL
Vdc Signal
CFM
from CO2
Control
10
450
425
8.87
400
8.31
375
7.61
6.73
350
325
5.91
300
5.15
275
4.58
250
4.06
225
2.91
2.57
200
175
2.24
1.74
150
125
0.96
0.77
100
FIGURE 19A
To adjust the airflow ventilation rate (NO CO2
CONTROL/NON-MODULATING) , determine the "FLOW
INDEX" needed for the intake and exhaust blowers for
the CFM you require.
1.> Locate two 0-10Vdc Motor Control Boards in control panel
2.> On intake Motor Control Board, observing "GREEN STATUS
LIGHT", turn manual adjust potentiometer (with a small phillips-head
screwdriver) "CCW" to increase "FLOW INDEX" or CW to reduce
"FLOW INDEX" to match desired setting. (NOTE: After long pause,
the green status light will blink long-blinks for the "TEN COUNT" of
the "FLOW RATE INDEX", which then is immediately followed by
fast blinks which indicate the second digit. For example, a Flow
Index of 23 would be two long blinks, followed by 3 fast blinks of
the "GREEN STATUS LIGHT".)
3.> On exhaust Motor Control Board, observing "GREEN STATUS
LIGHT", turn manual adjust potentiometer (with a small phillips-head
screwdriver) "CCW" to increase "FLOW INDEX" or CW to reduce
"FLOW INDEX" to match desired setting. (Same GREEN STATUS
LIGHT blink (refer to Step #5))
FIGURE 19B
After determining the air volume
rates needed for the intended
application (Maximum &
Minimum), the table
immediately to the left will allow
for you to program your CO2
control output voltages in
correlation to the CO2 levels you
wish to control when Bard Part #
8403-067 CO2 Control is applied.
Manual
2100-597