Viessmann Vitocal 222-S Installation And Service Instructions For Contractors page 76

Compact heat pump, split version
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Commissioning the system
Parameters for circulation pumps and other components
Heating circuit pump
Parameter
"System definition"
Ó
"System scheme 7000"
DHW circulation pump
Parameter
Extended menu
Ó
"Time program DHW circulation"
Installation kit with mixer for heating circuit M2/HC2
Parameter
"System definition"
Ó
"Type of assembly kit 7044"
"Internal hydraulics"
Ó
"Rated output heating circuit pump HC2 734A"
Mixer extension kit for heating circuit M3/HC3
Parameter
"System definition"
Ó
"System scheme 7000"
Remote control for heating/cooling circuit or Vitocomfort 200
Parameter
"Heating circuit 1"/"Heating circuit 2"/"Heating circuit 3"
"Remote control 2003"
or
"Remote control 3003"
or
"Remote control 4003"
Room temperature sensor for separate cooling circuit
Parameter
"Cooling"
Ó
"Ranking room temp sensor separate cooling circuit 7106"
76
(cont.)
Setting
Setting
Set a time program.
Setting
"1"
Set the required rated output in %.
Setting
With heating circuit HC3
Note
Set rotary switch S1 in the extension
kit to "2": See "Mixer extension kit" in-
stallation instructions.
Setting
Ó
"1"
Note
To assign a heating circuit, set the
code at the remote control:
See "Vitotrol" installation instructions.
Setting
"0" Connection F16
"1" Heating circuit HC1
"2" Heating circuit HC2
"3" Heating circuit HC3
"4" Do not adjust.
With heating circuit HC1 without mix-
er
or
With heating circuit HC2 with mixer
or
With heating circuit HC3 with mixer