Commissioning, inspection, maintenance
Commissioning the system
Parameters for circulation pumps and other components
Heating circuit pump
Parameter
"System definition"
Ó
"System scheme 7000"
DHW circulation pump
Parameter
Extended menu
Ó
"Time program DHW circulation"
Installation kit with mixer for heating circuit M2/HC2
Parameter
"System definition"
Ó
"Type of assembly kit 7044"
"Internal hydraulics"
Ó
"Rated output heating circuit pump HC2 734A"
Mixer extension kit for heating circuit M3/HC3
Parameter
"System definition"
Ó
"System scheme 7000"
Remote control for heating/cooling circuit or Vitocomfort 200
Parameter
"Heating circuit 1"/"Heating circuit 2"/"Heating circuit 3"
"Remote control 2003"
or
"Remote control 3003"
or
"Remote control 4003"
Room temperature sensor for separate cooling circuit
Parameter
"Cooling"
Ó
"Ranking room temp sensor separate cooling circuit 7106"
76
(cont.)
Setting
■
■
■
Setting
Set a time program.
Setting
"1"
Set the required rated output in %.
Setting
With heating circuit HC3
Note
Set rotary switch S1 in the extension
kit to "2": See "Mixer extension kit" in-
stallation instructions.
Setting
Ó
"1"
Note
To assign a heating circuit, set the
code at the remote control:
See "Vitotrol" installation instructions.
Setting
"0" Connection F16
"1" Heating circuit HC1
"2" Heating circuit HC2
"3" Heating circuit HC3
"4" Do not adjust.
With heating circuit HC1 without mix-
er
or
With heating circuit HC2 with mixer
or
With heating circuit HC3 with mixer