Viessmann Vitocal 222-S Installation And Service Instructions For Contractors page 43

Compact heat pump, split version
Table of Contents

Advertisement

Electrical connection
Indoor unit: Luster terminals (signal and safety connections)
Set the required parameters during commissioning:
See page 73 onwards.
Terminals
Function
X3.1
Switched phase
X3.6
Power-OFF (jumper fitted at the fac-
X3.7
tory)
G
X3.8
Type AWBT(-M)-E-AC:
X3.9
Frost stat
and/or
Contact humidistat 230 V~
Or jumper
Type AWBT(-M)/AWBT(-M)-E:
Jumper
X40.L1
Heat pump control unit power supply:
Phase L1
X40.
?
X40.N Neutral conductor terminal
(cont.)
Earth conductor terminal
Explanation
Via control unit ON/OFF switch
Note
Observe the total load 1000 W of all connected compo-
nents.
Requires floating contact:
Closed: Heat pump operational
Open: Heat pump shut down
Breaking capacity 230 V~, 0.15 A
Remove jumper when connecting.
Note
No parameters need to be set
The compressor is "forced" off as soon as the contact
opens.
The power-OFF signal switches off the power supply
to the relevant components, subject to the power sup-
ply utility.
For the instantaneous heating water heater, the
stages to be switched off can be selected (parameter
"Output for instant. heating water heater at pow-
er-OFF 790A").
The power supply for the heat pump control unit
(3 x 1.5 mm
2
) and the cable for the power-OFF signal
can be combined in a single 5-core cable.
For further information regarding power-OFF: See
chapter "Power supply".
In connection with Smart Grid:
Do not connect the power-OFF signal.
Do not remove jumper.
Requires floating contact:
Closed: Safety chain has continuity
Open: Safety chain interrupted; heat pump shut down
Breaking capacity 230 V~, 0.15 A
Connection:
Connected in series if both safety components are in-
stalled
Insert jumper if no safety components are instal-
led.
Power supply 230 V~: See page 49 onwards.
Installation sequence
43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents