Viessmann Vitocal 222-S Installation And Service Instructions For Contractors page 22

Compact heat pump, split version
Table of Contents

Advertisement

Installation sequence
Installing the indoor unit
Minimum room height
A
Fig. 17
A
Indoor unit
Finished floor level or top edge of platform for
B
unfinished floors
Pressure points
Ø d
b
Fig. 18
Partition joint with edge insulation strip as part of
A
the floor construction
a
439 mm
b
506 mm
c
670 mm
d
64 mm
22
(cont.)
B
Minimum room height a depends on the hydraulic con-
nection set used.
Hydraulic connection set
For installation on finished walls, for
upward connection
For installation to the left or right on
finished walls
Note
If applicable, remove the packaging box upwards
before installation.
Note
Observe the permissible floor load.
Level the appliance horizontally.
If the adjustable feet are used to compensate for an
uneven floor (max. 10 mm), distribute the pressure
load on the individual feet evenly.
Minimum
room height a
in mm
2100
2000